Trane Tracer AH.540 Installation Owner Diagnostics

Configurable air handling unit controller
Hide thumbs Also See for Tracer AH.540:
Table of Contents

Advertisement

Installation
Owner
Diagnostics
Tracer
Tracer
Configurable Air Handling
Unit Controller
AH.540
AH.541
CNT-SVX05A-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane Tracer AH.540

  • Page 1 Installation Owner Diagnostics Tracer AH.540 ™ Tracer AH.541 ™ Configurable Air Handling Unit Controller CNT-SVX05A-EN...
  • Page 2 ©American Standard Inc. 2000...
  • Page 3: Table Of Contents

    Contents Introduction ..................1 Supported Products ................2 Packaged Climate Changer™ Air Handling Units........ 2 Modular Climate Changer™ Air Handling Units........2 T-Series Climate Changer™ Air Handling Units ........2 Features ....................3 Termination board ................4 Controller board .................5 Physical specifications ..............6 Board dimensions ................6 Termination board..............
  • Page 4 Contents Outdoor air temperature ..............18 Mixed air temperature ..............18 Duct static pressure................18 On/cancel buttons................19 Zone sensor ..................20 Space temperature measurement ............ 20 Zone sensor setpoint adjustment ............. 20 Fan mode switch ................22 On/cancel buttons................22 Zone sensor communication jack .............
  • Page 5 Contents Variable air volume control ..............45 Duct static pressure control ............45 Supply fan operation................45 Constant volume operation .............46 Variable air volume operation ..........46 Valve operation ..................46 Steam valve cycling..............47 Face and bypass damper operation...........47 Outdoor air damper operation ............48 Mixed air temperature control..........48 Economizer operation..............49 Low ambient damper lockout..........50 Exhaust fan operation................50...
  • Page 6 Contents Test push button..............64 Service push button..............64 Green Status LED ..............65 Yellow Comm LED ..............65 Manual output test................65 Test sequence ................ 66 Minimum timers ..............67 Required inputs for unit operation ............ 67 Diagnostics ..................67 Translating multiple diagnostics..........
  • Page 7: Introduction

    The configurable air handling unit controller is also available as the Tracer AH.541 field-installed air handling unit controller (St. Paul, Minnesota). The features and functions of the Tracer AH.541 are identical to those of the Tracer AH.540 described in this manual. CNT-SVX05A-EN...
  • Page 8: Supported Products

    ™ T-Series Climate Changer Air Handling Units The Tracer AH.540 controller availability on the T-Series Climate Changer air handlers is limited to the features and functions provided by the controller. See the Features section for more information. Manufacturing Location: Lexington, Kentucky...
  • Page 9: Features

    Features ™ Table 1 — Tracer AH.540 features and control modes Constant volume space Constant volume Variable air volume temperature control discharge air control control Fan control On/Off On/Off Variable Duct static pressure con- trol Hydronic cooling Hydronic heating Steam heat Face and bypass heating X Ventilation control Economizer damper...
  • Page 10: Termination Board

    Termination board Analog Outputs Binary Outputs Analog Inputs Power Comm 5 Communication Terminals Duct Static Pressure Input Binary Inputs CNT-SVX05A-EN...
  • Page 11: Controller Board

    Controller board RED Service LED Supply Fan Service Push Button Status LED Yellow Comm LED Test Push Button Exhaust Fan Green Status LED Status LED ID Label CNT-SVX05A-EN...
  • Page 12: Physical Specifications

    Physical specifications Board dimensions Termination board Height: 3.5 inches (88.9 mm) Width: 8.0 inches (203.2 mm) Depth: 1.0 inch (25.4 mm) Controller board Height: 4.3 inches (109.2 mm) Width: 8.0 inches (203.2 mm) Depth: 2.0 inches (50.8 mm) Operating environment -40°...
  • Page 13: Binary Outputs

    TB25-2 BO 6 Not used TB26-1 Not used Not used (Note 1) TB26-2 Note 1: Terminals BO 3, BO 4, BO 5, and BO 6 do not serve any function of the Tracer AH.540 controller and are not used. CNT-SVX05A-EN...
  • Page 14: Analog Outputs

    Physical specifications Analog outputs The analog outputs are 0 to 10VDC. Table 3 — Analog outputs Description Function Factory Field Label Terminal Maximum terminals terminals function output rating AO 1 Supply fan TB11-1 0 to 10VDC 20mA speed TB11-2 Ground AO 2 Cool output TB12-1...
  • Page 15: Binary Inputs

    Physical specifications Binary inputs Each binary input associates an input signal of 0VDC with closed contacts and 24VDC with open contacts. If the wired binary device has closed contacts, a multimeter should measure less than 1.0VDC across the binary input terminals. If the binary input has opened, a multimeter should measure greater than 20VDC across the binary input terminals.
  • Page 16: Analog And Binary Outputs

    Analog and binary outputs The Tracer AH.540 is configured at the factory per unit configuration and order information. The controller is applied to air handling product configurations supporting analog modulating valves, economizer damper, and face and bypass damper. The controller supports a constant volume or variable air volume supply fan.
  • Page 17: Binary Inputs

    Not Used. The Tracer AH.540 controller has six available binary inputs. The binary inputs are connected to the Tracer AH.540 terminal board on inputs IN 7 through IN 12. Normally these inputs are factory-configured for the following functions.
  • Page 18: Low Temperature Detection

    Low temperature detection protects the coils of hydronic units. A low temperature detection device (freezestat) connected to binary input IN 7 detects the low temperature. The Tracer AH.540 controller can protect the coil using one binary input. When the controller detects the low temperature detection signal, the controller generates a diagnostic which disables the fan, opens all unit water or steam valves, and closes the outdoor air damper (when present).
  • Page 19: Occupancy

    Binary inputs Occupancy The Tracer AH.540 controller uses the occupancy binary input IN 9 for two occupancy-related functions. Standalone For standalone controllers (any unit not receiving a communicated occupancy request, typically from a building automation system), the occupancy binary input determines the unit's occupancy based on the hardwired signal. Normally, the signal is hardwired to a binary switch or clock.
  • Page 20: Generic Binary Input

    Filter status The filter status switch connected to binary input IN 11 detects a dirty air filter and indicates a need for maintenance. For Tracer AH.540 applications, a differential pressure switch detects filter status, with the high side of the differential being supplied at the filter inlet and the low side supplied at the filter outlet.
  • Page 21: Exhaust Fan Status

    Binary inputs Exhaust fan status The exhaust fan status binary input IN 12 indicates the presence of air flow through an exhaust fan associated with the controlled air handling unit. For Tracer™ AH.540 applications, a differential pressure switch detects exhaust fan status, with the high side of the differential being supplied at the outlet.
  • Page 22: Analog Inputs

    Tracer AH.540 interprets the signal as a timed override On request. The Tracer AH.540 uses the timed override On request (while the zone is unoccupied) as a request to go to the occupied bypass mode (occupied bypass).
  • Page 23: Local Setpoint

    Communicated setpoint setpoint input sensor thumb wheel Note 1: Communicated inputs to the Tracer AH.540 controller have precedence over locally wired inputs. Fan mode switch The fan mode analog input IN 3 responds to specific resistances corresponding to a fan mode switch provided with certain Trane zone sensors. The fan mode switch on a Trane zone sensor generates the fan mode signal.
  • Page 24: Discharge Air Temperature

    If the sensor returns to a valid input, the controller automatically allows the unit to resume operation. The Tracer AH.540 controller uses analog input 4 (IN 4) as the discharge air temperature input with a 10kΩ thermistor only. This sensor is hardwired and located downstream from all unit heating/cooling capacity at the unit discharge area.
  • Page 25: On/Cancel Buttons

    On/cancel buttons Momentarily pressing the On button during unoccupied mode places the controller in occupied bypass mode for 120 minutes. You can adjust the number of minutes the Tracer AH.540 is placed in the occupied bypass mode using ™ Rover service tool.
  • Page 26: Zone Sensor

    • Service pin message request Space temperature measurement Trane zone sensors use a 10kΩ thermistor to measure the space temperature. Typically, zone sensors are wall-mounted in the room and include a space temperature thermistor. A valid space temperature input is required for the controller to operate in constant volume space temperature control.
  • Page 27 Zone sensor The controller adds the absolute setpoint offset to occupied and occupied standby default setpoints to derive the effective setpoints as follows: Unoccupied cooling setpoint 85°F (same as default) Occupied standby cooling setpoint 77°F (default+1=77) Occupied cooling setpoint 75°F (default+1=75) Occupied heating setpoint 71°F (default+1=71) Occupied standby heating setpoint...
  • Page 28: Fan Mode Switch

    Auto fan mode of operation. On/cancel buttons Some Trane zone sensor modules include timed override On and Cancel buttons. Use the timed override On and Cancel buttons to place the controller in override (occupied bypass mode) and to cancel the override request.
  • Page 29: Zone Sensor Wiring Connections

    Zone sensor Zone sensor wiring connections Table 18 — Typical Trane zone sensor wiring connections with a fan mode switch Description Space temperature Common setpoint Fan mode Communications Communications Table 19 — Typical Trane zone sensor wiring connections without a fan mode switch...
  • Page 30: Communications

    Comm5 devices are given a unique address by the manufacturer. This address is called a Neuron ID. Each Tracer AH.540 controller can be identified by its unique Neuron ID, which is printed on a label on the controller’s logic board. The Neuron ID is also displayed when communication is established using Tracer Summit or Rover service tool.
  • Page 31: Wire Characteristics

    Communications Wire characteristics UCM communication-link wiring must be low capacitance, 18-gauge, shielded, twisted pair with stranded, tinned-copper conductors. For daisy chain configurations, limit the wire run length to 5,000 ft (1524 m). Trunk and branch configurations are significantly shorter (see Figure 3). Comm5 wire length limitations can be extended through the use of a link repeater.
  • Page 32: Termination Resistance Placement For Comm5 Links

    • If the link contains more than one type of wire, the link will probably have to be manually tuned. Trane recommends that only one type of wire be used for the Comm5 communication link •...
  • Page 33: Recommended Wiring Practices

    The following guidelines should be followed while installing communication wire. • Comm5 is not polarity sensitive. Trane recommends that the installer keep polarity consistent throughout the site • Only strip away 2" maximum of the outer conductor of shielded cable •...
  • Page 34: Power

    Power input from control box 24VAC transformer TB1-2 TB1-3 24VAC Accessory 24VAC power to other devices TB1-4 TB1-5 24VAC Accessory 24VAC power to other devices TB1-6 Figure 6 — Tracer AH.540 power requirement Line Voltage 24 VAC Termination Board Transformer (factory supplied) Chasis Ground AHU Controller...
  • Page 35: Input/Output Summary

    Input/output summary The controller includes the following input and output points: Power 24VAC NEC Class 2 Two binary outputs Supply fan start/stop (BO 1) Exhaust fan start/stop (BO 2) Five analog outputs Supply fan speed (AO 1) Cool output (AO 2) Heat output (AO 3) Face and bypass damper (AO 4) Outdoor air damper (AO 5)
  • Page 36: Sequence Of Operation

    The factory default settings are also based on the air handling unit configuration and order information. The Tracer AH.540 controller is configurable to operate in one of three air handling modes of operation: • Constant volume space temperature control •...
  • Page 37: Power Up Sequence

    Sequence of operation If a space temperature input is provided to the controller when configured as constant volume discharge air control or variable air volume control, the controller uses the space temperature to perform morning warm-up and daytime warm-up functions. Morning or daytime warm-up functions allow the controller to automatically change to heating if space temperature is less than the heating setpoint.
  • Page 38: Space Temperature Setpoint Operation

    Sequence of operation Space temperature setpoint operation The controller has three sets of possible heating and cooling setpoints: • Occupied • Occupied standby • Unoccupied In unoccupied mode, the controller always uses locally stored default unoccupied heating and cooling setpoints. These setpoints are configured at the factory prior to shipment.
  • Page 39 Sequence of operation The hardwired setpoint is used with the controller's occupancy mode (occupied, occupied standby, or unoccupied), the heating or cooling mode, the temperature deadband values, and the heating and cooling setpoints (high and low limits) to determine the controller's active setpoint Example continued: Assume a thumbwheel setpoint input of 73°F, resulting in an absolute setpoint offset of 1°F (73–72=1).
  • Page 40: Occupied And Unoccupied Operation

    The occupancy mode can be hardwired to the controller via the occupancy binary input or communicated to the controller. Occupied mode The Tracer AH.540 controller operates according to the configured control mode: • Constant volume space temperature control • Constant volume discharge air temperature control •...
  • Page 41: Unoccupied Mode

    In unoccupied mode the supply fan is off whenever the space temperature is between the unoccupied heating and cooling setpoints. If the space temperature rises above the unoccupied cooling setpoint the Tracer AH.540 turns on the supply fan and provides cooling at the discharge air cooling setpoint.
  • Page 42: Occupied Bypass Mode

    Occupancy—manual command Some communicating devices may request occupancy based on the information communicated in the network variable nvoOccManCmd. Trane systems and zone ™ sensors do not communicate this information to the controller, but the Tracer AH.540 controller accepts this network variable as communicated input nviOccManCmd.
  • Page 43: On And Cancel Buttons On The Zone Sensor

    Note 4: If the occupied bypass timer is not equal to zero, the effective occupancy will be occupied bypass. On and Cancel buttons on the zone sensor Some Trane zone sensor modules include timed override On and Cancel buttons. Use the timed override On and Cancel buttons to place the controller in override (occupied bypass mode) and to cancel the override request.
  • Page 44: Occupancy Binary Input

    Auto, the controller compares the active space setpoint and the active space temperature and decides if the space needs heating or cooling. The Tracer AH.540 controller must have a valid space temperature and discharge air temperature input to operate constant volume space temperature control.
  • Page 45: Control Gains

    Sequence of operation The capacity calculation, as a result of the discharge air control loop, is used to drive the air handling unit's actuators to maintain space temperature at the space temperature setpoint. Figure 7 — Space temperature control block diagram →...
  • Page 46 Auto mode, the unit switches to the desired mode based on the control algorithm. If the Tracer AH.540 controller is operating space temperature control, it uses the space temperature and space temperature setpoint to automatically determine heat or cool mode of operation.
  • Page 47: Cooling Operation

    Sequence of operation Figure 8 — Automatic heat/cool changeover logic example This is the point at which the cooling capacity equals 0%, space temperature is less than 0.5° F below the cooling setpoint, and the error integrator starts to add up. Error integration does not begin until the capacity is 0%.
  • Page 48: Heating Operation

    Figure 9 shows the steps the Tracer AH.540 controller takes to control discharge air. First the controller determines if a communicated discharge air heating setpoint and discharge air cooling setpoint are present.
  • Page 49 Sequence of operation The effective discharge air temperature setpoint is determined from: • communicated or configured discharge air setpoint value • minimum and maximum heat/cool setpoint limits • the effective heat/cool mode Example: Table 24 — Configuration parameters 55 ° F Discharge air cooling setpoint 68 °...
  • Page 50: Heating Or Cooling Control Mode Operation

    Sequence of operation Figure 9 — Discharge air temperature control flow diagram → Configured value: The communicated heat/cool setpoint value has discharge air heating setpoint precedence over the configured discharge air discharge air cooling setpoint temperature heat/cool setpoint → Communicated value: discharge air heating setpoint Discharge air heating Discharge air cooling...
  • Page 51: Variable Air Volume Control

    When a supply fan status binary input sensor is wired to the controller (IN 10) it is used to verify fan operation before heating and cooling start. Upon energizing the supply fan output (BO 1) the Tracer AH.540 controller waits a configurable time period (fan status delay) to allow the fan time to reach a desired air flow.
  • Page 52: Constant Volume Operation

    If the controller is wired to a Trane zone sensor, the user can change the supply fan operation through the fan mode switch (when present). When the fan mode switch is in the Off position, the controller shuts down the unit.
  • Page 53: Steam Valve Cycling

    (40°F default) at which the controller changes over to face and bypass heating operation. The face and bypass heat modulation setpoint can be changed using the Trane Rover™ service tool. When the outdoor air temperature is greater than 3°F above the face and bypass heating modulation setpoint, the hydronic heating valve is modulated to maintain discharge air temperature.
  • Page 54: Outdoor Air Damper Operation

    Default minimum damper positions are provided and can be changed using Trane's Rover service tool for occupied and occupied standby ventilation. The controller can also receive a communicated outdoor air damper minimum ™...
  • Page 55: Economizer Operation

    (either hardwired or communicated) or a communicated Enable command from ™ Tracer Summit , the Tracer AH.540 controller uses the modulating economizer damper as the highest priority source of free cooling. Economizing is possible during the occupied, occupied standby, unoccupied, and occupied bypass modes.
  • Page 56: Low Ambient Damper Lockout

    Sequence of operation Table 29 — Relationship between outdoor temperature sensors and damper position Outdoor air damper Outdoor air temperature Occupied or Occupied standby Unoccupied Occupied bypass No or invalid outdoor Open to occupied Open to occupied Closed air temperature minimum position standby minimum position...
  • Page 57: Electric Heat Operation

    Constant volume discharge air control or variable air volume control In these modes, the Tracer AH.540 controller requires a space temperature input (hardwired or communicated) and setpoint input (hardwired, communicated, or default value) to initiate the morning warm-up sequence of operation.
  • Page 58: Daytime Warm-Up

    (hydronic or steam) and Tracer AH.540 is configured for: • constant volume discharge air temperature control • variable air volume control. A communicated or wired space temperature is required for the Tracer AH.540 to initiate daytime warm-up. Daytime warm-up forces the controller into heating when the space temperature is below the effective heating setpoint by a temperature that is more than the configured daytime warm-up enable differential.
  • Page 59: Tracer Summit And Rover Output Overrides

    Example: The Tracer AH.540 is not able to run the air handling unit because the run/stop input is set to stop (supply fan is off). If the outdoor air temperature is below the freeze avoidance setpoint, the Tracer AH.540 opens all water valves.
  • Page 60: Water Valve Override

    Sequence of operation Duct static pressure (when present) is always controlled when the supply fan is running. Freeze avoidance in emergency override can force the heating and cooling valves open. Water valve override To support water balancing, the controller includes a communication variable (nviValveOverride) that allows a user to specify the desired state of all water valves.
  • Page 61: Calibration

    Calibration With Rover™ service tool, you can calibrate two of the controller’s analog inputs: space temperature, and setpoint. For each input, the calibration value is added to the measured value to determine the effective value. CNT-SVX05A-EN...
  • Page 62: Configuration

    Normally closed Normally closed Note 1: Trane’s Rover service tool uses the unit type to determine and download the proper default analog output configuration. For example, if you configure the controller's control mode to be constant volume space temperature control, Rover will not allow AO 1 to be configured for a supply fan speed output. Analog output 1 (AO 1) is only used when the controller is configured for variable air volume control.
  • Page 63 Outdoor air temp IN 6 Mixed air temp Duct static Duct static pressure Note 1: Trane’s Rover service tool uses the unit type to determine and download the proper default analog input configuration. Table 35 — Binary inputs Binary input Function...
  • Page 64 Disharge temperature setpoint low limit (Note 1) (1.7 to 65.6 ° C) Note 1: When the Tracer AH.540 controller is configured for constant volume space temperature control (control mode), the control algorithm is limited to calculating this high and low discharge air temperature setpoint.
  • Page 65 Configuration Table 43 — Duct static pressure Parameter Valid range Default value Duct static pressure high limit (Note 1) 0 to 5 inches WC 4 inches WC (0 to 1250 Pa) (1000 Pa) Duct static pressure setpoint 0 to 5 inches WC 1.5 inches WC (0 to 1250 Pa) (375 Pa)
  • Page 66: Location Identifier

    Configuration Table 48 — Steam valve cycling Parameter Valid range Default value Time period 0 to 10 minutes 5 minutes Duty cycle (Note 1) 0 to 100% Valve open position (Note 2) 0 to 100% Note 1: Duty cycle is the percentage of the time period the steam valve is open. Note 2: The steam valve open position can be set to a partially open position to prevent excessive steam coil temperatures.
  • Page 67: Application Information

    Application information Standalone Occupied/unoccupied You can configure the controller's binary input (IN 9) as an occupancy input to switch between occupied and unoccupied modes of operation. When IN 9 is configured as a normally open occupancy input, the standalone controller switches to occupied mode when IN 9 contacts are open.
  • Page 68: Standalone Peer-To-Peer

    Application information Standalone peer-to-peer ™ Tracer AH.540 controllers allow peer-to-peer (also referred to as master/slave) data communication. Data such as space temperature, setpoint, and occupancy can be shared from a master control to a peer control with or without the ™...
  • Page 69: Setpoint Operation

    You can achieve this by wiring the adjustable setpoint (typically included as a part of the Trane zone sensor module) to one controller—defined as the master. Next, use Rover™ to set up the master and one or more slaves to share that setpoint.
  • Page 70: Troubleshooting

    Troubleshooting Red Service LED Table 51 — Red Service LED activity Red LED Activity Description LED is off continuously after power Normal operation. is applied to the controller. LED is on continuously, even when Someone is pressing the Service push button or power is first applied to the controller.
  • Page 71: Green Status Led

    Troubleshooting Green Status LED The green Status LED is normally used to indicate whether or not the controller is powered On (24VAC). Table 52 — Green Status LED activity Green LED activity Description LED is on continuously. Power on (normal operation). LED blinks (one blink).
  • Page 72: Test Sequence

    Face and bypass full bypass 7: Exit (Note 4) Note 1: The following diagnostics cause the Tracer AH.540 to exit manual output test: • Duct Static Pressure High Limit • Low Supply Fan Air Flow • Low Temp Detect •...
  • Page 73: Minimum Timers

    Service required The controller disables certain sequences of operation only and attempts to maintain unit operation. For example, if the mixed air temperature sensor fails or is not wired, the Tracer AH.540 controller disables (does not allow) economizer operation. Informational This type of diagnostic does not affect controller operation.
  • Page 74 Troubleshooting Table 56 – (continued) Controller diagnostics Diagnostic or Condition Control type Supply Other outputs configuration (Enabled = Normal Operation) Low Exhaust Fan Air Flow CV Space temp control Enabled Valves Enabled (service required) CV Discharge air control Outdoor air damper Enabled Variable air volume control Face and bypass damper Enabled Exhaust fan Off...
  • Page 75: Translating Multiple Diagnostics

    Troubleshooting Translating multiple diagnostics The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur. Each diagnostic has a priority. When two diagnostic conditions exist, one diagnostic has priority over the other.
  • Page 76: Resetting Diagnostics

    Troubleshooting Resetting diagnostics A reset clears any latching diagnostics and allows the controller to try to run the air handling unit normally. If the latching condition is still present, the controller immediately shuts down the air handling unit. A reset will restart a unit that is running normally.
  • Page 77: Questionable Unit Operation

    Fan mode off When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the off position controls the unit off. Requested mode off You can communicate a desired operating mode (such as off, heat, and cool) to the controller.
  • Page 78 Refer to the Manual output test section. Fan mode off When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the Off position controls the unit off and closes the valves.
  • Page 79 Troubleshooting Table 62 — Outdoor air damper stays closed Probable cause Explanation Normal operation The controller opens and closes the outdoor air damper based on the control- ler's occupancy mode and fan operation. Normally, the outdoor air damper is open during occupied, occupied standby, and occupied bypass mode when the fan is running and closed during unoccupied mode unless the controller is economizing.
  • Page 80: Appendix

    Appendix Appendix Table 63 — Constant volume space temperature control operation based on the effective heat/cool output Application Heat/cool mode input Effective heat Unit Operation mode input (nviHeatCool) cool mode output (nviApplicMode) (nvoHeatCool) Auto Auto Determined by Fan Enabled controller Heating Enabled Cooling Enabled Damper Enabled...
  • Page 81 Appendix Table 62 — (continued) Constant volume space temperature control operation based on the effective heat/cool output Application Heat/cool mode input Effective heat mode input (nviHeatCool) cool mode output (nviApplicMode) (nvoHeatCool) Unit Operation Auto Not present Determined by Fan Enabled controller Heating Enabled Cooling Enabled...
  • Page 82 Heating Enabled Cooling Disabled Damper Enabled Note 1: Heating capacity can be used to control the discharge air temperature to the discharge air cooling setpoint. Table 65 — Trane zone sensor module hardwired setpoint adjustment Resistance setpoint 889.4 Ω 50 ° F 733.6 Ω...
  • Page 83 Appendix Table 66 — Hardwired 10k Ω thermistor values Resistance Temperature Resistance Temperature 87.5k Ω 0 ° F 10.0k Ω 77 ° F 74.6k Ω 5 ° F 9.3k Ω 80 ° F 63.8k Ω 10 ° F 8.2k Ω 85 °...
  • Page 84 Appendix CFR 47, Part 15, Subpart A, Class A Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 85 Index Active setpoint ..................... 33 Address of Comm5 devices ................24 AH.540 Analog inputs....................8 Analog outputs .....................8 Binary inputs ....................9 Binary outputs....................7 Communications..................24 Features ......................3 Occupancy modes ..................34 Specifications....................6 Supported products..................2 Analog input 01 ....................16 Analog input 02 ....................
  • Page 86 Index Binary input 12 ....................15 Binary inputs Configuration..................11, 57 Descriptions ....................9 List ....................... 29 Occupancy input..................13 Run/stop input .................... 12 Binary output 01 ....................45 Binary outputs Configuration....................10 Descriptions ....................7 List ....................... 29 Output overrides ..................10 Status LED ....................
  • Page 87 Index Cooling source configuration ................56 Damper ........................57 Configuration ....................57 Face and bypass damper operation............47 Operation..................... 50 Outdoor air damper operation ..............48 Troubleshooting..................72, 73 Daytime warmup ..................31, 52 Applications ....................61 Configuration ....................58 Device addressing ....................
  • Page 88 Index Economizing ......................49 Cooling requirements ................31 Effective setpoints ..................21, 33 Electric heat Operation ....................51 Emergency override ................... 53 Exhaust fan Configuration....................57 Operation ....................50 Status ......................15 External setpoint adjustment ................. 32 Face and bypass damper Heat modulation..................
  • Page 89 Index Hardwired setpoint (IN 2) .................20 Heat/cool changeover ..................41 Heating mode ...................39, 42, 44 Heating source configuration ................56 Inputs required for unit operation ..............67 Inputs/outputs Ratings.......................7, 8 Summary..................... 29 Internal setpoint adjustment ................32 Local setpoint .......................17 Enable or disable ..................21 Location identifier ....................
  • Page 90 Index Neuron ID ......................24 nviApplicMode ....................74, 76 nviHeatCool ......................74 nviSetpoint ..................... 17, 33 nviSetptOffset ..................... 33 nviSetptShift ......................33 nvoApplicMode ....................76 nvoHeatCool ....................74, 76 Occupancy binary input ..................38 Occupancy input ................... 13, 61 Occupancy modes ..................
  • Page 91 Index Effect on face and bypass damper operation........47, 59 Freeze avoidance .................. 53, 59 Output overrides ....................10 Using Tracer Summmit or Rover............... 53 Peer-to-peer communication ..............24, 62 Power connections ..................... 28 Power requirements .....................6 Power up sequence ....................31 Red Service LED activity ...................
  • Page 92 Index Measuring using a zone sensor ............16, 20 Setpoint configuration ................58 Setpoint operation ..................32 Setpoint selection..................32 Timed override requests................16 Space Temperature Failure diagnostic ............16 Standalone operation ..................61 Occupancy input..................13 Peer-to-peer communication..............62 Status LED ......................
  • Page 93 Index Valves Modulating valves ..................46 Operation..................... 46 Steam valve cycling................47, 60 Troubleshooting..................71, 72 Water valve override .................. 54 Variable air volume Control ....................30, 45 Fan operation ....................46 Morning warmup control ................51 Operation based on effective heat/cool output........76 .........................
  • Page 96 La Crosse For more information contact your local sales office or Since The Trane Company has a policy of continuous product and product data improvement, e-mail us at comfort@trane.com it reserves the right to change design and specifications without notice.

This manual is also suitable for:

Tracer ah.541

Table of Contents