Update the Display Original X-CODE to
Symbio Display X-CODE
When the display firmware is upgraded, revise the display
part X-Code to X13760359001 in order to avoid future
confusion when ordering replacement parts.
In order to do this, we print the correct X-Code on the 2
page of the CDUB nameplate. Cut this from the name plate
and put it on the back of the display. If there is an X-Code
presently on the display back, cover it with the new X-code
number.
Figure 9.
AdaptiView Symbio X-code
Figure 10. Remove existing UC800 controller in panel
Install New Symbio 800 Controller in Panel
Note: Symbio 800 controller should be mounted on the
door in CDUA and CVRE chiller retrofit panel.
1. Mount Symbio 800 controller on the din rail.
2. Mount Modbus distribution harness terminal close to
Symbio left, plug harness terminal to Symbio 800 P2
connector, please note this harness isn't required in
CVHM retrofit panel.
CDUB-SVN002B-EN

Shut Down Power

1. Using Lock out Tag out safety procedures, shut down
the chiller's main power.
2. Open all starter and control panel disconnect switches
and secure them in the open position.
nd
3. Confirm that the power is off to the control panel of the
chiller.
Remove the Existing UC800 controller and
Install New Symbio 800 Controller
Remove Existing UC800 Controller in Panel
Note: UC800 controller is mounted on the door in CDUA
chiller retrofit panel.
1. Unplug the terminal of IPC communication harness.
2. Unplug the USB terminal of USB cable.
3. Unplug the RJ45 terminal of ethernet cable.
4. Loosen the screw of din rail end stop.
5. Remove UC800.
3. Tighten the screw of din rail end stop.
4. Plug the terminal of IPC communication harness to
Symbio 800 P3 connector.
5. Plug the terminal of USB cable to Symbio USB
connector.
6. Plug the terminal of ethernet cable to Symbio 800 RJ45
No2 connector.