Trane Tracer Uc page 39

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Protocol
Set Up the Use Software Device ID
Specify a software device ID using the Tracer TU service tool tab Controller Settings screen on the
Controller Settings Utility tab, if the BACnet protocol is being used at the job location. A software
device ID is useful when integrating Trane equipment into a non-Trane environment.
1. Select the Use Software Device ID check box.
2. If no soft set ID is present, or if wanting to change the existing soft set ID:
3. If a soft set ID is present, and wanting to return it to a hard set device ID.
VAV-SVX07B-EN
Baud Rate: If the protocol is BACnet or Modbus, use this drop-down list to specify the baud
rate of the link, which depends on the network device to which the controller is being linked.
Device ID
– Current Device ID: Displays the Device ID of the controller. The default Device ID is set to
the unit controller MAC address set on the rotary dials. The Device ID can also be soft set.
– Rotary Dial Setting: Displays the controller's rotary dial setting.
– Use Software Device ID: If the BACnet protocol is being used, enter a soft set Device ID.
This is useful for integration with third-party equipment. (Select the check box to activate the
entry box.)
a. Select the Use Software Device ID check box.
b. Enter a new ID.
c. Click Send to Device.
d. Cycle the power to the controller to make the change effective.
a. De-select the Use Software Device ID check box.
b. Click Send to Device.
c. Cycle the power to the controller to make the change effective.
Tracer™ UC400 Controller Operations