Pressure Inputs; Binary Inputs; Binary Outputs; Analog Outputs - Trane Tracer Uc

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Overview

Pressure Inputs

Binary Inputs

Binary Outputs

Binary Outputs Type
BO1
Fan
BO2
Spare Relay
BO3
Spare Relay
BO4
Fan ON/Off
BO5
Heat stage 3 TRIAC
BO6
Heat stage 2/Water Valve Close TRIAC
BO7
Heat stage 1/Water Valve Open TRIAC
BO8
Air Damper Close TRIAC
BO9
Air Damper Open TRIAC

Analog Outputs

Note: For more information on wiring spare points, refer to the Tracer UC400 Programmable
12
P1;
– Supply airflow, pressure transducer
– From 0 to 2 in. water column (0 to 498 Pa)
P2;
– Spare (recommended for dual duct secondary airflow)
BI1;
– Occupancy
BI2;
– Spare
BI3;
– Spare
Output Rating
10A up to 277 Vac
10A up to 277 Vac
10A up to 277 Vac
24-27 Vac, 0.5A Resistive VA
24-27 Vac, 0.5A Resistive VA
24-27 Vac, 0.5A Resistive VA
24-27 Vac, 0.5A Resistive VA
24-27 Vac, 0.5A Resistive VA
24-27 Vac, 0.5A Resistive VA
AO1;
– Spare output.
– Voltage output is 0 to 10 Vdc, 500  minimum impedance.
– Current output is 4-20 mA, 500  max. impedance.
– Also can output 100 Hz PWM signal for control of a Trane fan-powered ECM fan setpoint
signal to the EC motor.
Note: ECM fan for future production.
AO2;
– Spare.
– Voltage output is 0 to 10 Vdc, 500  minimum impedance.
– Current output is 4-20 mA, 500  maximum impedance.
– Also used on Trane VAV units for SCR electric heat 0-to-10 Vdc modulation control.
Controller Installation, Operation, and Maintenance Manual (BAS-SVX20).
Pilot duty
10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac
10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac
10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac
VAV-SVX07B-EN