BACnet Networks Without a Tracer SC+ System Controller

On BACnet networks without a Tracer SC+ system controller, the Device ID can be assigned one of
two ways:

BACnet Networks With a Tracer SC+ System Controller

On BACnet networks with a Tracer SC system controller, the Device ID for the Symbio 210 controller
can be soft set by the system controller using the following scheme.
Note: The BACnet Device ID is displayed as the Software Device ID on the Tracer TU Controller

Device ID Assignment for BACnet MS/TP Devices

Each unit controller must have a unique BACnet device ID. Tracer SC+ automates the process by
calculating a unique device ID for each unit controller and then saving the device ID to memory in
each device.
BACnet MS/TP device IDs are calculated using the following three sets of values:
22
Ethernet cable connection from Symbio 210
It can be the same number as the MAC Address, determined by the rotary address dials on the
Symbio 210 controller. For example, if the rotary address dials are set to 042, both the MAC
Address and the BACnet Device ID are 042, OR
It can be soft set using Tracer TU service tool or Symbio UI. If the BACnet Device ID is set using
Tracer TU service tool or Symbio UI, the rotary address dials only affect the MAC Address, they
do not affect the BACnet Device ID.
Settings Page in the Protocol group.
The Tracer SC+ rotary switch value (1 to 419)
The Tracer SC+ BACnet MS/TP link number (1 to 3)
The unit controller rotary switch value (1 to 127)