Steps 10 To 14 - Monitored Outputs 1 To 5 - Siemens XC10 Series Installation, Commissioning Maintenance

Extinguishing control unit
Hide thumbs Also See for XC10 Series:
Table of Contents

Advertisement

Programming
12.6

Steps 10 to 14 - Monitored outputs 1 to 5

Description
Step
Option
10
Monitored output 1 : select the operation
01
Processing as "Sounder"
Active until "Silence/Re-sound" or "Reset" via non-monitored control input 1
11
Monitored output 2 : select the operation
01
Processing as "RT-alarm"
02
Processing as "Fire control A"
03
Processing as "Fire control B"
04
Processing as "Fire control C"
05
Processing as "Sounders"
06
Processing as "Sounder" except that:
- is activated continuously in state "Activated"
- is deactivated in state "Emergency Hold/Abort"
Application: additional wire for second tone sounder
07
Active in state "Mechanical blocked"
Application: use of a specific Warning Panel showing that extinguishing is blocked
08
Active in state "Automatic blocked" or "Manual blocked"
Application: specific Warning Panel for "Manual Blocked" or "Automatic Blocked"
09
Active in state "Automatic blocked" and "Manual blocked"
Application: specific Warning Panel for "Manual Blocked" and "Automatic Blocked"
12
Monitored output 3 : operation
Fire alarm
01
Not activated
02
Not activated
03
Not activated
04
Pulsating
13
Monitored output 4 : operation
01
Processing as "Actuators"
14
Monitored output 5 : operation
01
Processing as "Actuators"
Application: several actuators shared on 2 different lines and triggered at the same time
02
Processing as "Actuators"
Same as "Control line 4", but Pre-Discharged warning time is 0 second
Application: activation of a selector valve before a control valve
03
Processing as "Fire control A"
04
Processing as "Fire control B"
05
Processing as "Fire control C"
06
Active in state "Mechanical Blocked"
Application: use of a specific Warning Panel showing that extinguishing is blocked
07
Active in state "Automatic Blocked" or "Manual Blocked"
Application: use of a specific warning panel for "Automatic Blocked" or "Manual Blocked"
08
Active in state "Automatic blocked" and "Manual blocked"
Application: specific Warning Panel for "Manual Blocked" and "Automatic Blocked"
09
Not used (no EOL required)
54
Building Technologies
Fire Safety & Security Products
Evacuation
Continuous
Pulsating
Pulsating
Continuous
Emission
Continuous until reset
Continuous until reset
Continuous until "key 4" is pressed after reset
Continuous until reset
A6V10257473_b_en_--.doc
01.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1001-aXc1005-aXc1003-a

Table of Contents