XCA1031 common module description

Building Technologies
Fire Safety & Security Products
1
2
3
4
Control
Sector 1
cylinder
Sector 2
Sector 3
Loss of agent
A
Actuator
B
XCA1031
Inter-blocking
C
Communication (RS485)
D
Fig. 28
XC1003-A, typical multi-sector installation
All inputs/outputs, except output D, are monitored by the module itself. The power
supply is provided by the first and the last XC1003-A control unit.
Input A:
-
used to connect the "loss of agent" monitoring devices (manometers, weighing
device) from the main cylinder bank as well as from the pilot cylinder
-
« Loss of agent » information as well as electrical fault (break or short circuit) on
the line is forwarded, via output D, to all the extinguishing control panels in
order to display « Loss of agent » or « General fault » (line fault)
Output B:
-
used to connect the control cylinder actuator
-
redundant so that an electrical fault (break or short circuit) on one line doesn't
affect any extinguishing process
-
controlled by reverse polarity lines
-
electrical faults (break or short circuit) are forwarded, via output D, to all the
extinguishing control panels in order to display « Actuators fault »
Input C:
-
receives the information that at least, one extinguishing control panel in the
network is activated
-
on receipt, the module transmits, via output D, the blocking information to all the
extinguishing control panels in order to display « Actuators disabled »
Flooding zone 1
Flooding zone 2
DV
EV
XCA1030
XCM1002
XCA1030
XC1003-A / Sector 1
XC1003-A / Sector 2
Multi-sector installation
Flooding zone 3
DV
DV
EV
EV
XCM1002
XCA1030
XCM1002
XC1003-A / Sector 3
A6V10257473_b_en_--.doc