Step 05 - Sounders

Description
Step
Option
05
Sounders: program the pattern
Fire alarm
01
Continuous
02
Pulsated slow
03
Pulsated fast
04
Pulsated slow
05
Continuous
06
Continuous
07
Pulsated slow
08
Not activated
09
Pulsated long
10
Pulsated fast
11
Pulsating fast
Pulsated fast =
Active 1 second / Inactive 1 second
Pulsated slow =
Active 1 second / Inactive 4 seconds
Pulsated long =
Active 4 seconds / Inactive 1 second
Note: according to EN 12094-1 paragraph 4.30.2, sounders activation during released condition shall be continuous
12.5

Steps 06 to 09 - Remote transmission

Description
Step
Option
06
RT-alarm: program the activation
01
Active in state fire alarm
02
Active in state fire alarm, activated, released
03
Active in state activated, released
04
Active in state released
05
Active in state fire alarm, activated, released, zone 4 in alarm condition
Application: transmit RT-Alarm as soon as the DM1103-L is activated, even if "Manual blocked" is selected
07
RT-fault : program the activation
01
Activation : without delay on any fault
Duration :
until buzzer silence
02
Activation : without delay on any fault
Duration :
until buzzer silence and fault elimination
03
Activation : after 3 mn, on any fault, if buzzer is not silenced
Duration :
until buzzer silence
04
Activation : after 3 mn, on any fault, if buzzer is not silenced
Duration :
until buzzer silence and fault elimination
05
Activation : without delay on any fault, disable, mechanical blocking, loss of agent, incorrect status
Duration :
until activation cause disappears
08
« Remote transmission » LED (9): activation and operation
01
Lights up on RT-alarm (Enable/Disable, via key 11, possible)
02
Lights up on RT-alarm and RT-fault (Enable/Disable, via key 11, possible)
03
Unused (key 11 disabled)
Application: Remote transmission not used [FR]
09
RT-Alarm and RT-Fault suppression when operating access level 2
01
Remote transmission not blocked
02
Remote transmission blocked
Application: avoid the remote transmission when the system is controlled by the operator
Building Technologies
Fire Safety & Security Products
Activated
Pulsated fast
Pulsated fast
Pulsated long
Continuous
Continuous
Continuous
Continuous
Continuous
Pulsated fast
Continuous
Continuous
outputs programmed as " Remote transmission" cannot be disabled
Emergency hold/abort
Pulsated slow
Pulsated slow
Pulsated fast
Pulsated slow
Pulsated slow
Continuous
Continuous
Pulsated slow
Pulsated slow
Continuous
Pulsating fast
Programming
Released
Pulsated fast
Continuous
Continuous
Continuous
Pulsated fast
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
53
A6V10257473_b_en_--.doc
01.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1001-aXc1005-aXc1003-a

Table of Contents