Xcm1002 - Siemens XC10 Series Installation, Commissioning Maintenance

Extinguishing control unit
Hide thumbs Also See for XC10 Series:
Table of Contents

Advertisement

Overview
4.5

XCM1002

Setting elements
X3
Internal buzzer Enable/Disable
X4
Type of power supply
X8
Operating access Level 2
X13
Relay contact type 1
(NO or NC)
X14
Relay contact type 5
(NO or NC)
X15
Relay contact type 4
(NO or NC)
X16
Relay contact type 3
(NO or NC)
X17
Relay contact type 2
(NO or NC)
Other elements
F1 / F2
Pluggable fuse 2 AF
F3
Pluggable fuse 1 AF
F4 / F5 / F6
Pluggable fuse 1 AT
S1
Reset
S18-1 / S18-2
Not used
16
Building Technologies
Fire Safety & Security Products
Fig. 5
XCM1002 board
Fuse for protection of control outputs 4 (F1) and 5 (F2)
Fuse for protection of 24V output
Fuse for protection of control outputs 1 (F4), 2 (F5) and 3 (F6)
Do not change (factory setting : OFF)
Jumper up (factory setting) : buzzer enabled
Jumper down : buzzer disabled (only for servicing)
Jumper up (factory setting) : FCP1004-E
Jumper down : do not use (for further use of external power supply)
Jumper on the right (factory setting) : Level 2 access using code
Jumper on the left : Level 2 access permanent
Jumper up : NC contact
Jumper down (factory setting) : NO contact
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
Jumper on the right : NC contact
Jumper on the left (factory setting) : NO contact
A6V10257473_b_en_--.doc
01.2010