Siemens XC10 Series Installation, Commissioning Maintenance page 66

Extinguishing control unit
Hide thumbs Also See for XC10 Series:
Table of Contents

Advertisement

Maintenance
LED
Designation
Color
20
Yellow
Actuators
21
Yellow
Fire controls
22
Yellow
RT-Fault
23
Yellow
RT-Alarm
25
Red
Zone 1
26
Yellow
Zone 1
27
Red
Zone 2
28
Yellow
Zone 2
29
Red
Zone 3
30
Yellow
Zone 3
31
Red
Manual release
32
Yellow
Manual release
66
Building Technologies
Fire Safety & Security Products
State
Significance
Fixed
SC
Slow
OL
Fixed
SC
Slow
OL
Fixed
SC
Slow
OL
Fast
Calibration error
Fixed
SC
Slow
OL
Fast
Calibration error
Fixed
Alarm < 15 s after reset
Fixed
SC
Slow
OL
Fixed
Alarm < 15 s after reset
Fixed
SC
Slow
OL
Fixed
Alarm < 15 s after reset
Fixed
SC
Slow
OL
Fixed
Enabled < 15 s after reset
Fixed
SC
Slow
OL
Any electrical fault (break or short circuit) on the following lines may have a
direct consequence on the extinguishing process, or in some cases prevent it.
- Detector lines
- Manual release line
CAUTION
- Monitored control output 1 to 5
- Monitored inputs 1 to 4
It is imperative to fix any fault in a short delay in order to not jeopardize an
extinguishing process.
Monitored output 2
Monitored output 3
Monitored output 4
Monitored output 5
Detection line 1
Detection line 2
Detection line 3
Manual release line
A6V10257473_b_en_--.doc