Connect the cable to the assigned connecting/terminal block.
Avoid placing copper cables where they may bend or strain fiber optic cables.
Trunk cables among network interface,
sneak fuse panel, and media gateway
The 1-pair of central office (CO) trunks are installed by the network provider in the green field. Up to 24
pairs may be terminated on each row of the 110-type terminal block. Tie trunks also appear in the green
field with up to eight 3-pair trunks terminated on each row of the 110-type terminal block.
WP-90929, List 1 and 3 concentrator cables can be used to connect the media gateway to the 110-type
terminal blocks in the purple field. The 1-pair patch cords/jumper wires are then run from the purple
terminal block rows to the green terminal block rows in order to establish the correct 3-pair modularity.
Installing cables between media gateway and
main distribution frame
1
Install D rings on the wall between the cable slack manager and the terminal/connecting blocks
mounted on the MDF.
2
Install a self-adhesive port label on the back of each connector on the connector cable. Position
the labels so the media gateway connector retainers do not cover them.
3
At the rear of the media gateway, connect one end of the connector cable to the assigned
connector.
4
Route the cable down the rear of the media gateway, through the cable slack manager, and to the
MDF.
5
At the MDF, connect the other end of the cable to the assigned terminal/ connecting block
connector.
6
Store the cable slack in the cable slack manager.
7
Repeat Steps 2 through 6 until all cables are installed.
Installing connector cables between auxiliary
cabinet (if used) and main distribution frame
Auxiliary equipment that connects to the MDF can be mounted inside the auxiliary cabinet. The
equipment connects to an ED-1E1443-10 (Group 1) intraconnection panel mounted in the cabinet. This
intraconnection panel consists of a 110-type 100-pair wiring block. Auxiliary equipment is connected to
the 110-type wiring block. The wiring block is pre-wired to four 25-pair female connectors mounted on
the outside rear of the cabinet.
1
Install "D" rings on the wall between the cable slack manager and the terminal/connecting blocks
mounted on the MDF.
2
Install a self-sticking port label on the rear of each connector on the B25A connector cable. See
Figure 68, Self-stick label on 25-pair cable connector,
3
Labels should be positioned so the cabinet connector retainers do not obscure them.
Installing the Avaya S8500 Media Server with an Avaya G650 Media Gateway
December 2003
Connecting the media gateway to the main distribution frame
on page 190.