Quick Start Guide - Emerson Rosemount 3051S Quick Start Manual

High static differential pressure transmitter
Hide thumbs Also See for Rosemount 3051S:
Table of Contents

Advertisement

Quick Start Guide

Signal termination
Every fieldbus segment requires terminators at each end of the segment.
Failure to properly terminate segments may cause communication errors with
devices on the segment.
Transient protection
Transient protection devices require the transmitter be grounded for proper
operation. Refer to
5.8.1 Grounding
Grounding terminations are provided on the sensor module and inside the
terminal compartment. These grounds are used when transient protect
terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the FIELD TERMINALS housing cover.
2.
Note
The terminals are not polarity sensitive. The cable shield should:
Connect the wiring pair and ground as indicated in
28
Figure 5-11
Be trimmed close and insulated from touching the transmitter
housing
Continuously connect to the termination point
Be connected to a good earth ground at the power supply end
for further information.
February 2019
Figure
5-11.
Rosemount 3051SHP

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3051shp

Table of Contents