Quick Start Guide

Figure 5-3: With Optional Process Temperature Connection
A. RL ≥ 250 Ω
B. Power supply
Note
Installation of the transient protection terminal block does not provide
transient protection unless the transmitter case is properly grounded.
5.3
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
sensor module and inside the terminal compartment. These grounds are used
when transient protection terminal blocks are installed or to fulfill local
regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in
The cable shield should:
20
Be trimmed close and insulated from touching the transmitter
housing
Continuously connect to the termination point
Be connected to a good earth ground at the power supply end
February 2019
B
A
Figure
5-4.
Rosemount 3051SHP