Figure 5-6: Rosemount 3051S Quick Connect Exploded View
A. Straight field wireable connector (part number 03151-9063-0001),
supplied by customer
B. Right angle field wireable connector (part number 03151-9063-0002),
supplied by customer
C. Quick Connect housing
D. Cordset, supplied by vendor
E. Coupling nut
F. Quick Connect coupling nut
Important
If Quick Connect is ordered as a Rosemount 300S spare housing or is removed
from the sensor module, follow the instructions below for proper assembly
prior to field wiring.
Procedure
1. Place the Quick Connect onto the sensor module. To ensure proper pin
alignment, remove coupling nut prior to installing quick connect onto
the sensor module.
2. Place coupling nut over quick connect and wrench tighten to a
maximum of 300 in-lb (34 N-m).
3. Tighten the set screw up to 30 in-lb using a 3/32-in. hex wrench.
4. Install cordset/field wireable connectors onto the Quick Connect. Do
not over tighten.
24
B
A
E
C
D
F
Rosemount 3051SHP