Set Switches And Jumpers - Emerson Rosemount 3051S Quick Start Manual

High static differential pressure transmitter
Hide thumbs Also See for Rosemount 3051S:
Table of Contents

Advertisement

Quick Start Guide
4

Set switches and jumpers

If alarm and security adjustment option is not installed, the transmitter will
operate normally with the default alarm condition alarm "high" and the
security "off".
Procedure
1. Do not remove the transmitter covers in explosive atmospheres when
the circuit is live. If the transmitters is live, set the loop to manual and
remove power.
2. Remove the electronics compartment cover. On the Plantweb housing
the cover is opposite the field terminals side, or on the junction box
housing remove the terminal block cover. Do not remove the housing
cover in explosive environments.
3. On the Plantweb housing, slide the security and alarm switches into
the preferred position by using a small screwdriver (An LCD display or
an adjustment module must be in place to activate the switches). On
the junction box housing pull the pins out and rotate 90° into desired
position to set the security and alarm.
4. Reinstall the housing cover so metal contacts metal to meet explosion-
proof requirements.
Figure 4-1: Transmitter Switch and Jumper Configuration
(Plantweb)
16
A. Meter/adjustment module
B. Security
C. Alarm
A
B
February 2019
C
Rosemount 3051SHP