Boiler temperature – the boiler should reach this temperature.
Start boiler pump - the pump will be switched on after reaching this temperature
Pump delay – pump off time after boiler shutdown
Maximum power of burner - determines the output of the burner
Exhaust-fan maximum power - determines the maximum output of the exhaust fan
Exhaust-fan minimum power - determines the minimum output of the exhaust fan
Exchanger cleaning worktime - is tme that the exchanger will be cleaned by turbulators
Exchanger cleaning interval - determines how often the exchanger has to be automatically
cleaned by turbulators
Pic. 95
Service parameters, page 2
Ignition retry numbers - if the first ignition is unsuccessful, further ignition attempts are made.
The number of ignition attempts is entered here
Maximum Power - the maximum power the burner should achieve
Maximum Ignition time– indicates the maximum acceptable time during which the heating
spiral will be turned on and the fan to ignite the pellets. If the pellets are not ignited during this
time, a repeated ignition process or failure is reported
Starting Feeding time 1 – is the time that the pellet feeder pours a certain amount of pellets
down into the burner for the first time
Starting Feeding time 2 – is the time that the pellet feeder fills a certain amount of pellets into
the burner if the pellets are not ignited during the Maximum Ignition time
Burner Cleaning worktime - duration of the automatic burner cleaning
Photocell Fire on – when the boiler exceeds this value it evaluates that the pellets have already
been ignited in the burner