10.2

Programmable Output Relay

Refer to the below steps to set up the user programmable relay.
1. Required UPS Software
Display Software: 1.00 (U50DFV01000) or later
Make sure 5000 UPS has the correct software for Display before proceeding. Display software version can also be
checked at Settings > DISP / REYE > 801 DFW Ver.
2. Log in as a Administrator (ADM on display)
At the far left of the display, there should be 4 quick access buttons. Press the button,
level. You will be prompted to enter a password. Enter Administrator password "ADMIN" as factory default. If successful,
press Quit to exit the password screen.
3. Set Output Relay
From Settings tab, go to Ctrl/Cfg button > 641 Output Relay 1. Choose a value between 1 and 23. Detail information for
each value can be found in table below. One the value has been selected, choose Write on the display to save. Set cor-
responding Output Relay 2 – 8 in command 642 – 648. To disable the relay, set the value to 0.
4. Log off
Press Bitmap Key button,
Please see Table 10.3 for details regarding the functions that are available for programming on the output relay board.
Code
Function
0
None
1 *
FAULT OCCURRED
2 *
WARNING OCCURRED
3
AC INPUT ABNORMAL
4
BYPASS ABNORMAL
5
BATTERY ABNORMAL
6
BATTERY LOW WARNING
7*
BATTERY SHUTDOWN
WARNING
38
on the display. Enter USER. Execute Write and if successful, Quit.
TABLE 10.3: OUTPUT RELAY FUNCTIONS & DESCRIPTIONS
Description
Activated when any fault occurs. This is the default setting on
OUT8.
Activated when any warning occurs.
Activated when the input voltage or
frequency is abnormal.
Activated when the bypass voltage or
frequency is abnormal.
Activated when the battery is abnormal. One or more of the
following three items will be indicated on the display when a
Battery Abnormal condition occurs: BATT_OH warning, BATT_
SD warning or BATT_DEP fault.
Activated when the battery voltage drops below voltage Low
Battery Detection level defined by Cmd#530 during inverter
operation. A LOW_BATT warning will be indicated on the dis-
play when this warning occurs. This level is set in the display's
Setup tab by an Authorized Toshiba Service Provider.
Activated when the battery voltage drops below Battery Shut-
down detection level voltage defined by Cmd#528 during
inverter operation. A BATT_SD warning will be indicated on
the display when this warning occurs. This level is set in the
display's Setup tab by an Authorized Toshiba Service Provider.
This is the default setting for OUT5.
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001