Important Safety Instructions

The following contains important instructions that should be followed during the installation, operation, and maintenance of
the 5000 Series UPS.
Misuse of this equipment could result in personal injury and/or equipment damage. In no event will
Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that
may come from the use of this equipment.
The UPS system output is equipped with four (4) internal breakers:
1) 3 Phase Primary Input
2) 1 Phase Static Bypass
3) 1 Phase Maintenance Bypass
4) 1 Phase Output
The maximum ambient operating temperature for the UPS is 104 °F (40 °C) at 100% load and 0.9 PF.
If the UPS is exposed to the same ambient temperature as the DC backup supply, the maximum operating ambient
temperature is:
Battery backup: 90 °F (32 °C) at 100% load and 0.9 PF. Table 3.1 lists the nominal battery voltage.
4
CAUTION
TABLE 3.1: UPS NOMINAL BATTERY VOLTAGE
Capacity
Nominal Voltage Float Voltage
15kVA
120 VDC
30kVA
120 VDC
50kVA
120 VDC
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
135 VDC
135 VDC
135 VDC