7.3

MBS Mimic Display

The following table identifies the location and components of the MBS Mimic Display on the MBS Cabinet.
No.
1
2
3
4
5
2
4
MBS MIMIC PANEL
22
TABLE 7.3: MBS MIMIC DISPLAY LOCATION AND IDENTIFICATION
Function
Maintenance Bypass
On LED
CB2 (Bypass Breaker)
LEDs
CB3 (Maintenance By-
pass Breaker) LEDs
CB1 (UPS Input
Breaker) LEDs
CB4 (UPS Output
Breaker) LEDs
1
3
5
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
Description
On – UPS is in Maintenance Bypass Operation.
Off – UPS is in Inverter or Static Bypass Operation
Green – CB2 is Closed
Red – CB2 is Open
Green – CB3 is Closed
Red – CB3 is Open
Green – CB1 is Closed
Red – CB1 is Open
Green – CB4 is Closed
Red – CB4 is Open
5000 SERIES 3P1 UPS