Advertisement

UPS.
5. If using the UPS to provide power to motors that require high starting current or with motors that require a
long starting time, call Toshiba support for guidance in oversizing the UPS for locked rotor current.
6. The maximum ambient operating temperature at 100% load and 0.9 PF is 104 °F (40 °C).
7. DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS.
8. DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS.
9. The capacitors in the UPS maintain a residual charge for a while after turning the UPS off. Wait five (5) min-
utes before opening cabinet. This allows the system capacitors to fully discharge.
10. DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative for repair
information.
11. Turn the power on only after securing ALL of the bay access doors.
12. DO NOT open any Power Electronics bay access doors to a system with 30/40/50kVA capacity when power is
on. 15kVA systems include a dead front to protect operators from energized power electronics.
13. If the UPS should emit smoke or an unusual odor or sound, turn the power off immediately.
14. Warning signs should be placed on or near the load as a notification that the load is being powered by the
UPS.
15. Additional warnings and notifications shall be posted at the equipment installation location as deemed re-
quired by Qualified Personnel.
18
While operating in the inverter mode, placing the input breaker in the "OFF"
position will switch the UPS to the DC supply backup mode.
The output of the UPS will continue uninterrupted to the load. The unit must be in the
bypass mode at the time that the breaker is placed in the "OFF" position for the UPS
to shutdown power to the load.
After an Emergency Power Off (EPO), DO NOT reset the breaker until the UPS
internal circuits have been fully discharged.
The UPS could be damaged if the unit is not fully discharged before the breaker is
reset.
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001