4.2

Inspection/Storage

Inspection
Upon receipt of the UPS, perform an inspection for shipping damage should be performed. Use caution when removing the
unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original
crating and packing materials for return to the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate and Bill of Lading conform to the order
specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
These instructions apply to installations that have already been through initial Start-up with Toshiba Service. For installations
that have not been through Start-up, arrange the intial power up with Toshiba Service.
Storage Preparation
1) Follow battery manufacturer storage recommendations for any batteries in the UPS system.
2) Stop the UPS.
3) Place the UPS Main Circuit Breaker and Bypass Circuit Breaker switch in the "OFF" position.
Storage Conditions
For best results, store the UPS in the original shipping container.
Storage temperature range: -4 to 104 °F (-20 to 40 °C)
The optimum storage temperature is 70 °F (21 °C). At higher ambient temperature backup
batteries will require recharging more frequently during storage (refer to battery manufacturer
recommendations for details).
Avoid the following storage locations:
Locations that are subject to extreme temperature changes or high humidity
Locations that are subject to high levels of dust or metal particles
Locations that are subject to excessive vibration
Locations that are subject to inclement weather or exposure to water.
Inclined floor surfaces
Falling Particles
8
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001