4.4

Transporting By Crane

Crane should be operated by personnel familiar and qualified with movement of equipment like the UPS.Cables should have
sufficient load ratings and be of the same length. Ensure the suspension cables are hooked at eyebolts. See Figure 4.4
Use a spreader bar between the Front and rear pair of lifting eye cables as needed to avoid bending or damaging the fan
exhaust hood(s). Use spreader bars where determined to be necessary. Keep the angle less than 60° between cables.
Figure 4.5 and Figure 4.6 show unacceptable lifting practices.
Refer to Appendix A - Weight and Dimension for UPS cabinet.
Keep UPS leveled when lifting. DO NOT swing or tilt the UPS. Minimize the impact when lowering the UPS to the floor.
Figure 4.7 and Figure 4.8 show examples of acceptable and unacceptable operations.
Less than 60°
FIGURE 4.4: CABLES AND EYEBOLTS TO LIFT THE UPS
More than 60°
Uneven Cables
FIGURE 4.5: ANGLE MORE THAN 60°
FIGURE 4.6: UNEVEN CABLES
FIGURE 4.7: UNACCEPTABLE OPERATION
FIGURE 4.8: ACCEPTABLE OPERATION