Plus Series Specifications (W/Output Isolation Transformer) - Toshiba 1400SE Series Operation Manual

Single phase - .6/.8/1.0/1.2/1.5/2.0/2.4 kva, single phase - .6/.8/1.0/1.5 kva plus
Table of Contents

Advertisement

TOSHIBA
4.0
Specifications
4.2

Plus Series Specifications (w/output isolation transformer)

Input
Battery
Battery backup time when fully charged
with 0.7 power factor at 77° F (25° C)
Output
Output voltage regulation
Output voltage waveform
Rated load power factor
Voltage transient characteristic
Rated output current (rms)
Maximum output current (peak)
Inverter overload capacity
Environment
Switches
Interfaces
Fault detect and input power loss
Options
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
(*****) Output voltage and capacity derated for 50 Hz output (model # UC1A1A010C6TB only).
MODEL NUMBER
UC1A1A006C6TB
CAPACITY
600 VA (0.42 kW)
Input voltage
Single phase, 120 Vac, +10% to -30% (*)
Input frequency
45 to 65 Hz
Input capacity
Input power factor
Approximate unity (0.98 to 1.0)
Battery rated voltage
10 min. at full load (**) 10 min. at full load (**)
30 min. at half load (**) 30 min. at half load (**) 30 min. at half load (**)
Recharge time
Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries
Sealed lead-acid
Output voltage
Single-phase, 120 volts
Within +/- 3%, steady state
Output frequency(*****)
50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Common mode
Less than 0.5V peak
Normal mode
Less than 10V peak
0.7 lagging (0.6 to 1.0)
+/- 5% under 100% load step change
150% for 60 seconds
Crest factor
3.0
Operating temperature
32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude(****)
Less than 3000 ft (1000 m) above sea level
External dimensions
7.06W x 20.44D x 14.63H in (179W x 519D x 371H mm)
Net weight
80 lb (36.4 kg)
Acoustical noise
45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
Bypass switch
Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
IBM (TM) AS/400
Pins 5 through 9
LAN Manager
Pins 2 and 3
Pins 1 and 4
RS232 ASCII
Pins 1 through 8
Software for unattended
computer shutdown
Contact Toshiba for details on this option
External battery pack
Contact Toshiba for details on this option
UC1A1A008C6TB
800 VA (0.56 kW)
600 VA
800 VA
36 Vdc
48 Vdc
5.0A
6.7A
15.0A
20.0A
85 lb (38.6 kg)
83%
83%
DB9 male connector
DB9 female connector (Pin 9 not used)
4 - 4
UC1A1A010C6TB
1000 VA (0.7 kW)
1000 VA
48 Vdc
10 min. at full load (**)
8.3A
25.0A
92 lb (41.8 kg)
85%