Storage/Operating Environment

5.1

Inspection/Storage

Inspection
Upon receipt of the battery cabinet, an inspection for shipping damage should be performed. Use caution
when removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping,
keep all original crating and packing materials for return to the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
1) The 440B battery cabinet should be charged for 24 hours to fully charge the batteries.
2) Stop the battery charger.
3) Place both 440B Main Circuit Breaker switches in the "OFF" position.
Storage Conditions
• For best results, store the battery cabinet in the original shipping container and place
on a wood or metal pallet
• Storage temperature range: 32 to 104 °F (0 to 40 °C)
• The optimum storage temperature is 70 °F (21 °C). A higher ambient temperature will
require recharging batteries more frequently during storage
Avoid the following storage locations:
• Locations that are subject to extreme temperature changes or high humidity
• Locations that are subject to high levels of dust or metal particles
• Locations that are subject to excessive vibration
• Inclined floor surfaces
5.2

Storage Environment

Observe the following when storing the battery cabinets.
Store battery cabinet indoors.
Temperature fluctuations should be minimized.
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60%.
Humidity must not exceed 90%.
Avoid locations where battery cabinet may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
4400 Series UPS Battery Cabinet Installation and Operation Manual – 69445-005