1.0

Inspection / Storage / Disposal

1.1

Inspection of the New Battery System

Upon receipt of the Battery System, a careful inspection for shipping damage should be made.
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during
shipment, keep all original crating and packing materials for return to the shipping agent. The
equipment warranty will not apply to units which are damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to
the order specifications.
1.2

Storage of Battery Equipment

If the Battery System is to be subjected to long or short term storage, the following guidelines should be
used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles.
3) Storage on inclined floor surfaces or in sites subject to excessive vibration.
Before storing:
1) Charge the system's batteries.
2) Place the Battery System's input switch (MCCB-C) in the OFF position.
Storing:
1) Store within a temperature range of -4 to 104 °F (-20 to 40 °C).
2) For best results, store the Battery System in the original shipping container and place on a wood or
metal pallet.
3) The optimum storage temperature is 70 °F (21 °C). Higher ambient temperatures cause UPS
batteries to need recharging more frequently.
4) If stored in an ambient temperature under 68 °F (20 °C); recharge the batteries every 9 months.
5) If stored in an ambient temperature of 68 to 86 °F (20 to 30 °C); recharge the batteries every 6
months.
6) If stored in an ambient temperature of 86 to 104 °F (30 to 40 °C); recharge the batteries every 3
months.
1.3

Disposal

Please contact your state environmental agency for details on disposal of electrical components and
packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly. Please help our Earth by
contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba
toll-free at (877) 867-8773 for more information about recycling.