Storage/Operating Environment; Inspection/Storage; Storage Environment - Toshiba G9000 SERIES Installation And Operation Manual

Slim maintenance bypass
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

5

Storage/Operating Environment

5.1

Inspection/Storage

Inspection
Upon receipt of the Slim MBS, an inspection for shipping damage should be performed. Use caution when
removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping,
keep all original crating and packing materials for return to the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
Place all MBS Circuit Breaker switches in the "OFF" position.
Storage Conditions
• For best results, store the Slim MBS cabinet in the original shipping container and
place on a wood or metal pallet
• Storage temperature range: 32 to 104 °F (0 to 40 °C)
• Avoid the following storage locations:
• Locations that are subject to extreme temperature changes or high humidity
• Locations that are subject to high levels of dust or metal particles
• Locations that are subject to excessive vibration
Inclined floor surfaces
5.2

Storage Environment

Observe the following when storing the Slim MBS.
Store indoors.
Temperature fluctuations should be minimized.
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60% without
condensation.
Humidity must not exceed 90%.
Avoid locations where the Slim MBS cabinet may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
Avoid locations that are subject to excessive vibration.Avoid inclined floor surfaces.
G9000 Slim MBS Installation and Operation Manual – 96011-000
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents