Annex 3: System Turn Off Progress List - Pylontech PowerCube-X1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-X1:
Table of Contents

Advertisement

Annex 3: System Turn OFF Progress List

Tick after
No.
completion
1
2
3
4
5
Soft-off the PCS through PCS's control panel.
Turn off the switch between PCS and this battery string
(PowerCube-X1), or turn off the power switch of PCS, to
make sure no current through this battery string.
Turn off all the "Power Switch" of the BMS.
Turn off the "Power Switch" of the MBMS.
Turn off the UPS. (If configured.)
z
The UPS can turn on to check the equipment (PCS
or battery system etc.). Otherwise must turn off the
UPS to save its power.
Item
28 / 28
Remark
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
19PIXV0703

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents