LIGHTGUIDE CABLE INTERCONNECT TERMINAL (LCIT)
The LCIT must be installed within 100 feet of related module control and TMS cabinets at
the central and remote locations. A 1/2-inch plywood backboard and mounting hardware
must be provided locally.
WARNING: The LCIT is 12 inches deep. Choose a location so that the LCIT
will be out of the way of traffic.
Install the LOT (Figure 6) as follows:
1. Mark the location of the 134A mounting bracket holes on the 1/2-inch plywood
backboard.
2. Make sure that the plywood backboard is mounted on the wall so that it will not
interfere with the 134A hole locations. Mount this backboard using standard procedures
for the type of wall used.
3. Mount the 134A mounting bracket (using hardware provided with the 134A) to the
plywood backboard in the location marked in Step 1.
4. Mount the LCIT to the 134A mounting bracket with hardware provided.
5. Attach ED-1E466 Group 212 label, and write the LCIT number on the LCIT Number
label (factory attached to the LCIT) in the locations shown in Figure 6.