PID control enhanced functions

• PID control enhanced functions can be used to perform PID control according to applications. (For the details
of the PID control, refer to page 378 of the Instruction Manual (Detailed).)
Pr.
Name
1361
Detection time for PID
A440
output hold
1362
PID output hold range
A441
1363
PID Priming time
A447
1364
Stirring time during sleep
A448
1365
Stirring interval time
A449
1366
Sleep boost level
A627
1367
Sleep boost waiting time
A628
1368
Output interruption
A629
cancel time
111
Check valve deceleration
F031
time
1369
Check valve closing
A446
completion frequency
1370
Detection time for PID
A442
limiting operation
1371
PID upper/lower limit pre-
A443
warning level range
PID measured value
1372
control set point change
A444
amount
PID measured value
1373
control set point change
A445
rate
1374
Auxiliary pressure pump
A450
operation starting level
1375
Auxiliary pressure pump
A451
operation stopping level
1376
Auxiliary motor stopping
A414
level
Initial
Setting
value
range
Set the time from when the deviation falls within the PID
5 s
0 to 900 s
output hold range until the PID output is held.
0 to 50%
Set the range in which the PID output is held.
9999
9999
The PID output holding is disabled.
Set the time from when the priming operation starts until
0 to 360 s
the main pump starts.
9999
9999
The PID priming pump function is disabled.
15 s
0 to 3600 s
Set the stirring time.
0 h
0 to 1000 h
Set the interval time for the stirring operation.
Increase the set point before the PID output suspension
0 to 100%
function is activated.
9999
9999
The PID sleep boost function is disabled.
0 s
0 to 360 s
Set the waiting time for the sleep boost operation.
Set the time from when the deviation reaches the output
0 s
0 to 360 s
interruption cancel level until the output is started.
Set the deceleration time for the check valve
0 to 3600 s
deceleration function.
9999
9999
The check valve deceleration function is disabled.
Set the frequency at which the check valve deceleration
0 to 120 Hz
stops.
9999
9999
The check valve deceleration function is disabled.
Set the time from when the measured value input
0 s
0 to 900 s
exceeds the Pr.131 or Pr.132 setting until the FUP or
FDN signal is output.
Set the operation range for the PID upper/lower limit
0 to 50%
pre-warning function.
9999
The PID upper/lower limit pre-warning function is
9999
disabled.
Set the set point change amount for the PID upper/lower
5%
0 to 50%
limit pre-warning operation.
Set the set point change rate for the PID upper/lower
0%
0 to 100%
limit pre-warning operation.
900 to
Set the deviation level for operating the auxiliary
1000%
1100%
pressure pump.
900 to
Set the deviation level for stopping the auxiliary
1000%
1100%
pressure pump.
Set the level for stopping the auxiliary motor by the PID
0 to 100%
overpressure control function.
9999
9999
The PID overpressure control function is disabled.
3
Description
BCN-C22005-703
Refer
to
page
4
6
5
8
9
8, 9,
10,
11
9
9,
11
7
8