Appendix
Appendix 1
The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free movement of the equipment, whose
safety is ensured, in the EU territory.
Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997, compliance with the Low Voltage Directive,
another EU Directive, has been also legally required. When a manufacturer confirms its equipment to be compliant with the EMC Directive and the Low Voltage
Directive, the manufacturer must declare the conformity and affix the CE marking.
• The authorized representative in the EU
The authorized representative in the EU is shown below.
Name: Mitsubishi Electric Europe B.V.
Address: Gothaer Strasse 8, 40880 Ratingen, Germany
• Note
We declare that this inverter conforms with the EMC Directive in industrial environments and affix the CE marking on the inverter. When using the inverter in a
residential area, take appropriate measures and ensure the conformity of the inverter used in the residential area.
 EMC Directive
We declare that this inverter conforms with the EMC Directive and affix the CE marking on the inverter.
• EMC Directive: 2004/108/EC
• Standard(s): EN61800-3:2004 (Second environment / PDS Category "C3")
• This inverter is not intended to be used on a low-voltage public network which supplies domestic premises.
• Radio frequency interference is expected if used on such a network.
• The installer shall provide a guide for installation and use, including recommended mitigation devices.
Note:
First environment
Environment including residential buildings. Includes buildings directly connected without a transformer to the low voltage power supply network which supplies
power to residential buildings.
Second environment
Environment including all buildings except buildings directly connected without a transformer to the low voltage power supply network which supplies power to
residential buildings.
 Note
Set the EMC filter valid and install the inverter and perform wiring according to the following instructions.

This inverter is equipped with an EMC filter. Enable the EMC filter. (For details, refer to the Instruction Manual (Detailed).)

Connect the inverter to an earthed power supply.

Install a motor and a control cable written in the EMC Installation Manual (BCN-A21041-204) and Technical News (MF-S-114, 115) according to the instruction.

Confirm that the inverter conforms with the EMC Directive as the industrial drives application for final installation.
 Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-5-1) and affix the CE marking on the
inverters.
 Outline of instructions

Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the earth. Connect the equipment to the earth securely.

Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)

Use the cable sizes on
• Surrounding air temperature: 40°C (104°F) maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.

Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the screw, be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on

Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.

This product can cause a d.c. current in the protective earthing conductor. Where a residual current-operated protective (RCD) or monitoring (RCM) device is used for
protection in case of direct or indirect contact, only an RCD or RCM of Type B is allowed on the supply side of this product.

Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the power supply), overvoltage category III (usable
with the earthed-neutral system power supply, 400 V class only) and pollution degree 2 or lower specified in IEC60664. An insulating transformer needs to be installed
in the input side of the FR-F820 series inverters.
• To use the inverter of FR-F820-01250(30K) or higher and FR-F840-00770(37K) or higher (IP00) under the conditions of pollution degree 2, install it in the enclosure of
IP 2X or higher.
• To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• To use the inverter of FR-F820-00930(22K) or lower and FR-F840-00620(30K) or lower (IP20) outside of an enclosure in the environment of pollution degree 2, fix a
fan cover with fan cover fixing screws enclosed.

On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
Instructions for compliance with the EU Directives
page 8
under the following conditions.
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00105(2.2K) to 00250(5.5K)
FR-F840-00083(3.7K), 00126(5.5K)
page
8.
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00340(7.5K) to 00930(22K)
FR-F840-00170(7.5K) to 00620(30K)
27