The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay output has basic isolation from the inverter
internal circuit.)

Control circuit terminals on

Environment (For the detail, refer to the Instruction Manual (Detailed).)
LD rating: -10 to +50°C (14 to 122°F)
Surrounding air temperature
SLD rating: -10 to +40°C (14 to 104°F)
Ambient humidity
95% RH or less
Maximum altitude
2500 m (8202 feet)
 Wiring protection
Class T, Class J, Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.T or UL 489 Molded Case Circuit Breaker (MCCB) must
be provided.
FR-F820-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse Maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F820-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse Maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse Maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse Maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)


Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 264 V Maximum.
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 550 V or 600 V Maximum.
28
page 5
are safely isolated from the main circuit.
During Operation
00046
00077
00105
00167
(0.75K)
(1.5K)
(2.2K)
(3.7K)
240 V or more
15
20
30
40
60
15
20
20
30
50
15
15
25
40
60
00930
01250
01540
01870
(22K)
(30K)
(37K)
(45K)
240 V or more
225
300
350
400
500
200
250
300
350
400
225
300
350
450
500
00023
00038
00052
00083
(0.75K)
(1.5K)
(2.2K)
(3.7K)
500 V or more
6
10
15
20
30
6
10
10
15
25
15
15
15
20
30
00930
01160
01800
02160
(45K)
(55K)
(75K)
(90K)
500 V or more
200
250
175
200
250
300
350
225
250
450
450
500
In Storage
-20 to +65°C (-4 to +149°F)
95% RH or less
2500 m (8202 feet)
00250
00340
00490
00630
(5.5K)
(7.5K)
(11K)
(15K)
80
150
175
200
70
125
150
200
80
110
150
190
02330
03160
03800
04750
(55K)
(75K)
(90K)
(110K)
500
600
700
700
900
1000
00126
00170
00250
00310
(5.5K)
(7.5K)
(11K)
(15K)
40
70
80
90
35
60
70
90
40
60
70
90
02600
03250
03610
04320
(110K)
(132K)
(160K)
(185K)
(220K)
400
500
600
700
During Transportation
-20 to +65°C (-4 to +149°F)
95% RH or less
10000 m (32808 feet)
00770
(18.5K)
00380
00470
00620
00770
(18.5K)
(22K)
(30K)
(37K)
110
150
175
100
125
150
100
150
175
04810
05470
06100
06830
(250K)
(280K)
(315K)
800
900
1000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents