Drive The Motor; Components Of The Operation Panel (Fr-Du08) - Mitsubishi Electric FR-F820-00046 Instruction Manual

Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

Operation panel (FR-DU08)
6

DRIVE THE MOTOR

6.1
Operation panel (FR-DU08)
6.1.1

Components of the operation panel (FR-DU08)

No.
Component
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
(k)
(l)
(m)
16
DRIVE THE MOTOR
(j)
(k)
(l)
(m)
Name
PU: ON to indicate the PU operation mode.
EXT: ON to indicate the External operation mode. (ON at power-ON in the initial setting.)
Operation mode indicator
NET: ON to indicate the Network operation mode.
PU and EXT: ON to indicate the External/PU combined operation mode 1 or 2.
MON: ON to indicate the monitoring mode. Quickly flickers twice intermittently while the protective function is
Operation panel status
activated.
indicator
Slowly flickers in the display-off mode.
PRM: ON to indicate the parameter setting mode.
IM: ON to indicate the induction motor control.
Control motor indicator
PM: ON to indicate the PM motor control.
The indicator flickers when test operation is selected.
Frequency unit indicator
ON to indicate frequency. (Flickers when the set frequency is displayed in the monitor.)
Shows the frequency, parameter number, etc.
Monitor (5-digit LED)
(Using Pr.52, Pr.774 to Pr.776, the monitored item can be changed.)
PLC function indicator
ON to indicate that the sequence program can be executed.
FWD key: Starts forward rotation. The LED is on during forward operation.
REV key: Starts reverse rotation. The LED is on during reverse operation.
The LED flickers under the following conditions.
FWD key, REV key
• When the frequency command is not given even if the forward/reverse command is given.
• When the frequency command is the starting frequency or lower.
• When the MRS signal is being input.
Stops the operation commands.
STOP/RESET key
Resets the inverter when the protection function is activated.
The setting dial of the Mitsubishi inverters. The setting dial is used to change the frequency and parameter
settings.
Press the setting dial to perform the following operations:
Setting dial
• To display a set frequency in the monitoring mode (the setting can be changed using
• To display the present setting during calibration
• To display a fault history number in the faults history mode
Switches to different modes.
Switches to the easy setting mode by pressing simultaneously with
MODE key
Holding this key for 2 seconds locks the operation. The key lock is invalid when
to the Instruction Manual (Detailed).)
Enters each setting.
If pressed during operation, the monitored item changes.
SET key
Pr.52
(Using
can be changed.)
Goes back to the previous display.
ESC key
Holding this key for a longer time changes the mode back to the monitor mode.
Switches between the PU operation mode, the PUJOG operation mode, and the External operation mode.
PU/EXT key
Switches to the easy setting mode by pressing simultaneously with
Cancels the PU stop also.
(a)
(b)
(c)
Description
Pr.774-Pr.776
and
, the monitored item
(d)
(e)
(f)
(g)
(h)
(i)
Pr.992
.)
.
Pr.161
="0 (initial setting)". (Refer
When the initial setting is set
Output frequency
Output current
Output voltage
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents