Terminal connection diagrams
 CA type
Sourse logic
Main circuit terminal
Control circuit terminal
Three-phase
AC power
supply
Control input signals
(No voltage input allowed)∗3
Forward rotation start
Reverse rotation start
Start self-holding selection
Multi-speed
selection
Second function selection
Terminal 4 input selection
(Current input selection)
Common for external power
supply transistor
Contact input common
24VDC power supply
24V external power
Common terminal
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ∗6
Terminal 4 input
(Current input)
Connector for plug-in option connection
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common

For the FR-F820-03160(75K) or higher, the FR-F840-01800(75K) or higher, always connect a DC reactor (FR-HEL), which is available as an option. (To select a DC
reactor, refer to
page
When a DC reactor is connected to the FR-F820-02330(55K) or lower or the FR-F840-01160(55K) or lower, if a jumper is installed across the terminals P1 and P/+,
remove the jumper before installing the DC reactor.

When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189). (Refer to

Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage, set the voltage/current input switch OFF. To
input a current, set the voltage/current input switch ON. Terminals 10 and 2 are also used as a PTC input terminal. (Pr.561) (Refer to the Instruction Manual (Detailed).)

It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.

Do not use terminals PR and PX. Do not remove the jumper connected to terminals PR and PX.

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196). (Refer to

The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194). (Refer to

No function is assigned in the initial status. Assign the function using Pr.186 CS terminal function selection. (Refer to
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, separate the main circuit cables at the input side from
the main circuit cables at the output side.
• After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting
holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.
6
WIRING
DC reactor
(FR-HEL)∗1
Jumper
Earth
(Ground)
P1
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
∗2
S1/L21
Main circuit
Earth
(Ground)
Control circuit
STF
STR
STP(STOP)
RH
High speed
RM
Middle speed
RL
Low speed
∗4
JOG
Jog operation
RT
MRS
Output stop
RES
Reset
AU
CS
∗10
SD
PC
+24
supply input
SD
∗5
10E(+10V)
OFF
10(+5V)
3
DC0 to 5V
2
2
DC0 to 10V selectable
DC0 to 20mA
5
1
(Analog common)
DC0 to ±10V
Auxiliary
(+)
1
DC0 to ±5V selectable
(-)
input
DC4 to 20mA
(+)
4
DC0 to 5V
(-)
DC0 to 10V
connector 1 connector 2
connector 3
Shorting
24V
wire
PC
S1
Output shutoff
S2
circuit
SIC
SD
25, and select one according to the applicable motor capacity.)
Brake unit
(Option)
Jumper
Earth
(Ground)
P/+
PX∗7 PR∗7 N/-
U
Inrush current
V
limit circuit
W
ON
EMC filter
ON/OFF
connecter
OFF
C1
B1
Relay output 1
(Fault output)
A1
C2
B2
Relay output 2
A2
RUN
Running
SU
Up to frequency
IPF
Instantaneous
power failure
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink/source common
24V
PU
Voltage/current
connector
input switch
F/C
ON
(CA)
USB A
2
4
connector
Initial value
∗5
USB
AM
mini B
connector
5
Initial value
∗5
TXD+
Initial value
TXD-
selectable
∗5
RXD+
RXD-
SG
Terminating
VCC
resistor
So
Safety monitor output
SOC
Safety monitor output common
FR-F820-00770(18.5K) to 01250(30K),
FR-F840-00470(22K) to 01800(75K)
DC reactor
(FR-HEL)∗1
Brake unit
(Option)
Jumper
P1
P/+
P3
PR∗7 N/-
Motor
M
Earth (Ground)
Relay output∗8
Open collector output∗9
(+)
Analog current output
(0 to 20mADC)
(-)
(+)
Analog signal output
(DC0 to ±10V)
(-)
RS-485 terminals
Data
transmission
Data
reception
GND
5V
(Permissible load current 100mA)
page
18.)
page
18.)
page
18.)
page
18.)