Connection Diagram; Configuration; Step/Direction Controller Connection Diagram - THOMSON Omnidrive Series Installation Manual

Table of Contents

Advertisement

8-14
Application and Configuration Examples

Connection Diagram

Intro
Step/Dir
Generator
Close to ENABLE Drive
Close to RESET Fault
Close to Follow
External I/O
12-24 VDC
Power Source
Note 1. Refer to Figure 6.23 - Figure 6.30 and for additional details on the Control Interface Cable.

Step/Direction Controller Connection Diagram

F
8.4
IGURE

Configuration

Carefully check all connections before entering these parameters.
1. Switch the AC Power to ON and verify:
2. Start OMNI LINK on the PC.
3. Choose Cancel from the Drive Select dialog box.
4. Select PC Set Up from the Communications menu in OMNI LINK to display the personal com-
puter's communication settings.
5. Verify the communications port settings of the PC match those of the drive.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
DRIVE
J5
XMT
2 RCV
RCV
3 XMT
COM
5 COM
J1
STEP+
14 AX+
STEP–
15 AX–
DIR+
16 BX+
DIR–
17 BX–
20 ENABLE
21
FAULT
RESET
26 I/O PWR
32 INPUT1
5 I/O PWR
6 I/O COM
Status LED is green. Refer to "Status indicator" on page 10-1 for an explanation of the dis-
play codes.
If the settings are correct, select OK in the Port – Settings dialog box.
If the settings are different, correct the Port – Settings to allow communications with the
drive.
Factory default communications Port – Settings for the drive are:
– Baud Rate: 9600
J2
Motor
Encoder
TB1
Phase R 6
Phase S 7
Phase T 8
Mtr Gnd 9
L1
3
L2/N
4
Gnd
5
100-240 VAC
50/60 Hz
Single Phase
Power Source