4. Parameter Descriptions
[19]
Warning
[20]
Alarm_Trip
[21]
Alarm_TripLock
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
LogicRule 0
[27]
LogicRule 1
4
[28]
LogicRule 2
[29]
LogicRule 3
[30]
SL Timeout0
[31]
SL Timeout1
[32]
SL Timeout2
[33]
DigitalInput_18
[34]
DigitalInput_19
[35]
DigitalInput_27
[36]
DigitalInput_29
[38]
DigitalInput_33
[39]
StartCommand
[40]
DriveStopped
13-41 Logic Rule Operator 1
Array [4]
Disabled
*
[0]
[1]
And
[2]
Or
[3]
And not
[4]
Or not
[5]
Not and
[6]
Not or
[7]
Not and not
[8]
Not or not
13-42 Logic Rule Boolean 2
Array [4]
13-43 Logic Rule Operator 2
Array [4]
*
Disabled
[0]
[1]
And
[2]
Or
[3]
And not
[4]
Or not
52
A warning is active.
A trip alarm is active.
A trip lock alarm is active.
Use result of comparator 0 in logic rule.
Use result of comparator 1 in logic rule.
Use result of comparator 2 in logic rule.
Use result of comparator 3 in logic rule.
Use result of logic rule 0 in logic rule.
Use result of logic rule 1 in logic rule.
Use result of logic rule 2 in logic rule.
Use result of logic rule 3 in logic rule.
Use result of timer 0 in logic rule.
Use result of timer 1 in logic rule.
Use result of timer 2 in logic rule.
Use value of DI 18 in logic rule.
Use value of DI 19 in logic rule.
Use value of DI 27 in logic rule.
Use value of DI 29 in logic rule.
True
This event is
, if frequency converter is started by any means (digital input or other).
True
This event is
, if frequency converter is stopped or coasted by any means (digital input or other).
Select first logical operator to use on boolean inputs from par. 13-40 and 13-42.
Ignores parameters 13-42, 13-43 and 13-44.
Evaluates expression [13-40] AND [13-42].
Evaluates expression [13-40] OR [13-42].
Evaluates expression [13-40] AND NOT [13-42].
Evaluates expression [13-40] OR NOT [13-42].
Evaluates expression NOT [13-40] and [13-42].
Evaluates expression NOT [13-40] OR [13-42].
Evaluates expression NOT [13-40] AND NOT [13-42].
Evaluates expression NOT [13-40] OR NOT [13-42].
Select second boolean input for selected logic rule.
See par. 13-40 for choices and descriptions.
Select second logical operator to use on boolean inputs calculated in par. 13-40, 13-41, and 13-42 and the
boolean input from par. 13-42.
Ignores parameter 13-44.
Evaluates expression [13-40/13-42] AND [13-44].
Evaluates expression [13-40/13-42] OR [13-44].
Evaluates expression [13-40/13-42] AND NOT [13-44].
Evaluates expression [13-40/13-42] OR NOT [13-44].
MG.02.C4.02 - VLT is a registered Danfoss trademark