Danfoss VLT Micro Drive FC 51 Series Programming Manual page 40

Hide thumbs Also See for VLT Micro Drive FC 51 Series:
Table of Contents

Advertisement

VLT Micro Drive FC 51
6-15 Terminal 53 High Ref./Feedb. Value
Range:
*
50.000
[-4999.000 - 4999.000]
6-16 Terminal 53 Filter Time Constant
Range:
*
0.01 s
[0.01 - 10.00 s]
6-19 Terminal 53 Mode
Option:
*
Voltage Mode
[0]
[1]
Current Mode
4.7.4. 6-2* Analog Input 2
Parameters for configuring scaling and limits for analog input 2, terminal 60.
6-22 Terminal 60 Low Current
Range:
*
0.14 mA
[0.00 - 19.90 mA]
The value must be set to min. 2 mA in order to activate the Live Zero Timeout function in par. 6-01.
6-23 Terminal 60 High Current
Range:
*
20.00 mA
[0.10 - 20.00 mA]
6-24 Terminal 60 Low Ref./Feedb. Value
Range:
*
0.000
[-4999 - 4999]
6-25 Terminal 60 High Ref./Feedb. Value
Range:
*
50.00
[-4999 - 4999]
Function:
The scaling value corresponding to the maximum reference feedback value set in parameters 6-11 and 6-13.
Enter analog input scaling value.
Function:
A first-order digital low pass filter time constant for suppressing electrical noise in terminal 53. A high time
constant value improves dampening but also increases time delay through the filter.
Enter time constant.
Function:
Select the input to be present on terminal 53.
Par. 6-19 MUST be set according to Micro switch 4 setting.
Function:
This reference signal should correspond to minimum reference value set in par. 3-02.
Enter low current value.
Function:
This reference signal should correspond to the high current value set in par. 6-25.
Enter high current value.
Function:
The scaling value should correspond to the minimum reference feedback value set in par. 3-02.
Enter analog input scaling value.
Function:
The scaling value should correspond to the maximum reference feedback value set in par. 3-03.
Enter analog input scaling value.
MG.02.C4.02 - VLT is a registered Danfoss trademark
4. Parameter Descriptions
39
4