VLT Micro Drive FC 51
NB!
For par. 1-56 the following applies
[0]
[1]
[2]
[3]
4.2.4. 1-6* Load Dependent setting
Parameters for adjusting the load dependent motor settings.
1-60 Low Speed Load Compensation
Range:
*
100 %
[0-199 %]
1-61 High Speed Load Compensation
Range:
*
100 %
[0 - 199 %]
1-62 Slip Compensation
Range:
*
100 %
[-400 - 399 %]
1-63 Slip Compensation Time
Range:
0.10 s [0.05 - 5.00 s]
[4]
[5]
Function:
Use this parameter to gain optimum U/f characteristic when running at low speed.
Enter percentage in relation to load when motor runs at low speed.
Change-over point is automatically calculated based on motor size.
Function:
Use this parameter to obtain optimum load compensation when running at high speed.
Enter percentage to compensate in relation to load when motor runs at high speed.
Change-over point is automatically calculated based on motor size.
Function:
Compensation for load dependent motor slip.
Slip compensation is calculated automatically based on rated motor speed, n
NB!
This function is only active when par. 1-00,
[0], and when par. 1-01,
Function:
Enter slip compensation reaction speed. A high value results in slow reaction whereas a low value results in quick
reaction.
If low-frequency resonance problems arise, use longer time setting.
MG.02.C4.02 - VLT is a registered Danfoss trademark
4. Parameter Descriptions
.
M,N
Configuration Mode
, is set to
Motor Control Principle
VVC+
, is set to
[1].
4
Speed Open Loop
19