Parameter set 0

torque threshold M
If the actual torque value exceeds torque threshold M
M
³ M
(ID no. 333) in Class 3 Diagnostics.
d
dx
Display via LED H 401 red and via relay contacts X3:13 and X3:14 on printed circuit board
3.9211.

response time Pzkx (M
The response time specifies for how long the torque threshold must be exceeded before a
message is displayed.

voltage failure time
After a voltage failure that lasts not longer than the set voltage failure time, the drive starts
independently if the power supply of the controller isn´t disturbed and the pulse enable and
controller enable is given. After a voltage failure that lasts longer the drive sets a message
in Class 1 Diagnostics.
Controller BUS 6 T
Baumüller Nürnberg GmbH
dx
)
dx
5.94017.06
Parameters
, the drive sets the message
dx
83