Status messages

supply operating error
An operating error of the supply leads to pulse inhibit of the controller.
Bit no.
0
1

BUG hardware error
A hardware error leads to pulse inhibit of the controller.
Bit no.
0
1

error bar of I/O component boot
If an error occurs during the controller's boot procedure this error bar is activated and
controller enabling is not possible (controller inhibit).
NOTE
This ID no. can only be read by activation of key F4 on PC. Only the LED´s „Power" (green)
and „controller inhibit" (red) light on the unit.
Bit no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Controller BUS 6 T
Baumüller Nürnberg GmbH
Meaning
always 0
1: supply not ready for use
Meaning
reserved
1: supply not ready for use
Meaning
1: error of internal RAM
1: error of external RAM
1: memory submodule EPROM not available
1: memory submodule EEPROM faulty
1: memory submodule EEPROM not available
1: timeout at upper A/D converter
1: timeout at lower A/D converter
1: timeout at upper A/D converter
1: timeout at lower A/D converter
1: offset error at lower A/D converter
1: offset error at upper A/D converter
1: encoder module 1 not available
1: encoder module 2 not available
1: option board 1 not available
1: option board 2 not available
1: option board 3 not available
5.94017.06
Maintenance
105