Universal Motor Controller
UMC100-FBP
Technical Description
Overview:
Control function
Actuator 1
Actuator 2
Actuator 3
Actuator 4
Acutator 1
Open and Closed position via limit switches
Usage with limit switches
24V
DI0
12
13
Usage without torque switches
24V
DI0
12
13
UMC100-FBP
Torque open
-
Stop
-
Stop
Limit switches
DI1
14
Open
Closed
Limit switches
DI1
14
Open
Closed
Open <-> Closed
Limit open
Limit closed
Stop
Stop
Prepare
Prepare
Stop
Prepare
Prepare
Stop
DI0: Motor off, start only in Closed direction
DI1: Motor off, start only in Open direction
Torque
DI3: Fault: motor stops
DI3
16
Remark:
Open,
• Torque signals are not necessary but can
Closed
be used for surveillance.
• After switching off the motor continues
to run for some milliseconds due to its
rotating mass. Adjustment of the Closed
and Open limit switches is necessary to
achieve the correct end positions.
DI0: Motor off, start only in Close direction
DI1: Motor off, start only in Open direction
DI3
Remark:
16
Connection if torque contacts are not avail-
able
- 86 -
Torque closed
-
Stop
Stop
-
FieldBusPlug / Issue: 03.2012