Control Function Pole-Changing Starter - ABB UMC100-FBP Technical Description

Universal motor controller
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

Control Function Pole-Changing Starter

Use this function in a feeder that requires a two-pole or dahlander motor to start-stop in one direction of
rotation.
• Relay output DO0 is used by the control function to start the motor at speed one
• Relay output DO1 is used by the control function to start the motor at speed two
• Optionally DI0 can be used for contactor checkback supervision
• Optionally DI4/D3 can be used to start the motor at speed one/two and DI5 to stop it
• Optionally terminals named 24VDC Out (12) or DO2 (9) can be used as a fault output
The following diagram shows the UMC wired for two-pole operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0 and DO1. Two auxiliary contacts
are used for contactor checkback monitoring. The motor can be started locally via DI4 (speed one) or DI3
(speed two) and stopped via DI5. The remaining digital inputs can be freely used.
Two-Pole Motor
UMC-
PAN
Fieldbus
Plug
Circuit diagram of the UMC for controlling a two-pole motor. The checkback contacts k81/k91 are
optional.
UMC100-FBP
The voltage dip function is not supported in this control function
Set I
according to the motor nameplate
e2
GND
(24VDC)
24VDC
DO3
12
I
Lim
10 11
k81
0V
24VDC
Contactor
Supply
(e.g. 230VAC)
K91
K81
DOC DO0
DO1
DO2
5
7
8
9
UMC100
13 14
15
16
17
18
DI0
DI1 DI2 DI3 DI4 DI5
k91
Speed1 Stop
Speed2
- 82 -
L1, L2, L3
K81=spped one
K91=speed two
3
k81
k91
U1
U2
M
V1
V2
w1
w2
FieldBusPlug / Issue: 03.2012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents