A3 Technical Data

UMC100

Main Power Lines
Voltage (three-phase systems)
Conductor holes in the current transformers
Set current range for overload protection
Overload protection for three-phase motors
Trip classes, selectable by parameter
For trip class 40E selecting the contactor and the
protective elements with special care!
Tolerance of tripping time (incl. total ranges of cur-
rent, temperature 0-60°C, frequency 45-65 Hz)
Tripping time for phase loss
Accuracy class of the monitored current (range 50
to 200 % of I
Load per phase:
Frequency range
Short-circuit protection
Cross-section of lines
Vibration according IEC 60068-2-6
Shock according IEC 60068-2-27
FieldBusPlug / Issue: 03.2012
with I
> 0.5A)
e
e
Max. 1000 V AC
Attention:
For an U
of 8 kV and a voltage of 1000 V the
imp
device must be used according to Annex H
EN60947-1 in the range 600 V < U
(IT Network) only for overvoltage category II. Oth-
erwise overvoltage category III applies.
For voltages > 690V isolated wires have to be
used.
Max. diameter 11 mm incl. cable isolation
UMC alone: 0.24 - 63 A
UMC with provided current transformer:
60 - 850 A (see chapter 'Connecting External Cur-
rent Transformers')
Wire size has to be fixed acc. to IEC/EN 60204
Acc. to EN/IEC 60947-4-1
5E, 10E, 20E, 30E, 40E (acc. to EN/IEC 60947-4-1)
UMC alone: +/- 10 %
UMC with provided current transformer: +/- 14 %
Trip class:
5 approx. 1.5 s
10 approx. 3 s
20 approx. 6 s
30 approx. 9 s
40 approx. 12 s
UMC alone 3%
UMC with provided external
current transformer: 4%
Approx. 30 mΩ
45 - 65 Hz. Protection of frequency converters is
not allowed.
Provided by external short-circuit protection de-
vice), e. g. MO, MCB, MCCB or fuse. Refer also to
ABB coordination tables available here:
http://www.abbcontrol.fr/coordination_tables/
TABLES5.asp
Acc. to the rated motor current referring
EN/IEC 60947-1 and the specific installation
condition in EN/IEC 60204 or VDE 298-4 resp.
5 g (without LCD Panel)
15 g / 11 ms
- 141 -
<= 1000 V.
e
UMC100-FBP