ABB UMC100-FBP Technical Description page 130

Universal motor controller
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description
VI150 / VI155 Parameters
Para-
meter
Number
4
158
159
160
161
162
163
164
165
166
200
201
202
UMC100-FBP
Parameter
Description, Explanations
Name
VI15x
Specify if the module is con-
Enabled
nected to UMC
Nominal Line
Line to Line Voltage e.g.
Voltage
190V, 400V or 690V
U Low Trip
Value in % of U/U
Level
this value a trip is generated.
U Low Trip
Delay time until a low voltage
Delay
trip is triggered.
U Low Warn
Value in % of U/U
Level
this value a warning is gene-
rated.
U Low Warn
Delay time until a low voltage
Delay
warning is triggered.
U High Trip
Value in % of U/U
Level
this value a trip is generated.
U High Trip
Delay time until a high vol-
Delay
tage trip is triggered.
U High Warn
Value in % of U/U
Level
this value a warning is gene-
rated.
U High Warn
Delay time until a high vol-
Delay
tage warning is triggered.
PwrFactor
Power factor (cos phi).
Trip Level
Below this value a trip is
generated.
30 disables the function
PwrFactor
Delay time until a low power
Trip Delay
factor trip is triggered.
PwrFactor
Power factor (cos phi).
Warn Level
Below this value a warning is
generated.
30 disables the function
Options
0: Off
1: On
U
:
150...690V in steps of 1V
e
Default: 400V
. Below
70 ... 100%
e
70 disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
. Below
70 ... 100%
e
70 disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
. Above
100 ... 116% of U
e
of 1%
116% disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
. Above
100 ... 116% of U
e
of 1%
116% disables the function
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF
of 0.75
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.30 ... 1 in steps of 0.01
Unscaled: 30...100
Example: 75 means a PF
of 0.75
- 130 -
Adjustable via
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
in steps
All excluding
e
GSD-PDQ22
All excluding
GSD-PDQ22
in steps
All excluding
e
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
FieldBusPlug / Issue: 03.2012