PwrFactor
Delay time until a low power
Warn Delay
factor warning is triggered
U Imb. Trip
Voltage imbalance trip level
Level
20 disables the function
U Imb. Trip
Delay time until an imalance
Delay
trip is triggered
U Imb. Warn
Voltage imbalance warning
Level
level
20 disables the function
U Imb. Warn
Delay time until an imalance
Delay
warning is triggered
P Low Trip
Below this value a trip is
Level
generated
20 disables the function
P Low Trip
Delay time until an low po-
Delay
wer trip is triggered
P Low Warn
Below this value a warning is
Level
generated.
20 disables the function
P Low Warn
Delay time until an low po-
Delay
wer warning is triggered
P High Trip
Above this value a trip is
Level
generated
200 (1000%) disables the
function
P High Trip
Delay time until an high
Delay
power trip is triggered
P High Warn
Above this value a warning is
Level
generated
200% (1000) disables the
function
P High Warn
Delay time until an high po-
Delay
wer warning is triggered
Nominal Po-
Power factor value from the
wer Factor
name plate or data sheet of
the motor
0...25.5s in steps of 0.1s
Default: 3s
Unscaled: 0...255
Example: 20 means 2s
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
0.2 ... 20% in steps of 0.1%
Unscaled 2..200
0...25.5s in steps of 0.1s
Default: 1s
Unscaled: 0...255
Example: 20 means 2s
20 ... 100% in steps of 1%
0...255s in steps of 1s
Default: 5s
20 ... 100% in steps of 1%
0...255s in steps of 1s
Default: 5s
100 ... 1000%
Unscaled: 20...200
Example: 20 means 100%
0...255s in steps of 1s
Default: 10s
100 ... 1000%
Unscaled: 20...200
Example: 20 means 100%
0...255s in steps of 1s
Default: 10s
0.01 ... 1 in steps of 0.01
Default: 1
Unscaled: 1...100
Example: 75 means a PF
of 0.75
- 131 -
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
in steps of 5%
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
in steps of 5%
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22