Control Function Direct Starter (Dol) - ABB UMC100-FBP Technical Description

Universal motor controller
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

Control Function Direct Starter (DOL)

Use this function in a feeder that requires a motor to start/stop in one direction of rotation.
• Relay output DO0 is used from the control function.
• Optionally DI0 can be used for contactor checkback supervision
• Optionally DI4/DI5 can be used to start/stop the motor locally
• Optionally terminals named 24VDC Out (12) or DO2 can be used as fault output
The following diagram shows the UMC wired for DOL operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0. An auxiliary contact of K is used
by contactor checkback monitoring. The motor can be started locally via DI4 and stopped via DI5. The
remaining digital inputs can be freely used.
UMC-
PAN
Fieldbus
Plug
Circuit diagram of the UMC to control a motor in one direction of rotation. The checkback
contact k1 is optional.
FieldBusPlug / Issue: 03.2012
GND
(24VDC)
24VDC
DO3
12
I
Lim
10 11
13 14
DI0
0V
24VDC
- 73 -
Contactor
Supply
(e.g. 230VAC)
K1
DOC DO0
DO1
DO2
5
7
8
9
UMC100
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k1
Fwd Stop
L1, L2, L3
3
k1
3
M
UMC100-FBP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents