UMC100-FBP
Technical Description
Motor Management Parameters Continued
Para-
meter
Number
82
83
117,
118,
119
120,
121,
122
135/136
137/138
139/140
114,
115,
116
23
FieldBusPlug / Issue: 03.2012
Parameter
Description, Explanations
Invert control (ctrl) Inputs
Inv DI start
If inverted (Yes) the DI is nor-
input
mally closed. If not inverted
(No) it is normally open.
Inv DI stop
If inverted (Yes) the DI is nor-
input
mally closed. If not inverted
(No) it is normally open.
Multifunction Inputs: The following parameters are all related to DI0-DI2 which are called
multifunction inputs as their function can be adjusted in a wide range.
(1.13)
Multif. 0,1,2
Delay until the function of
delay
DI0,1,2 is triggered
Multif. 0,1,2
If DI0,1,2 is configured as
auto reset
external fault an auto reset
can be enabled.
Multif. 0,1,2
If DI0,1,2 is configured as an
fault text
external fault a text message
Line 1, Line 2
can be defined which is
shown on the LCD panel.
Multifunction
Function of DI0/1/2.
0,1,2
NC: Normally closed
NO: Normally open
1)
Motor running or stopped
2)
Always when the motor is
running
Extended
Checkback
The maximum delay between
time
the output relay was closed
until the checkback signal is
present (signal at DI0 present
or motor current > 20 %
depending on parameter
Checkback)
Options
No (0), Yes (1)
No (0), Yes (1)
0...25,5 in steps of 0,1s
Unscaled: 0...255
Example: A value of 5 means
500ms
No (0),
Yes (1)
Line one and line two with 8
characters each.
Default: „Fault DIx" where
x=0,1,2
Off (0):
Stop NC (1),
Stop NO (2),
Ext. Flt NC always
Ext. Flt NO always
Ext. Flt NC Motor on (5),
Ext. Flt NO Motor on (6),
Prep. emergency start NC (7),
Prep. emergency start NO (8)
Test position NC (9),
Test position NO (10),
Force local NC (11)
Force local NO (12)
Fault reset NC (13),
Fault reset NO (14),
Voltage DIP NC (15),
Voltage DIP NO(16),
CEM11 always
CEM11 after startup (Warn) (18),
CEM11 always
CEM11 after startup (Fault) (20)
0.1, 0.2, 0.3, 0.4 ,0.5 ... 25.5
in steps of 0.1s
Unscaled: 0...255
Example: A value of 5 means
500ms
- 123 -
Adjustable
via
All
All
PBDTM,
LCD Panel
UMC100-
PAN
All
1
(3),
1
(4),
2
(Warn) (17),
2
(Fault) (19),
All exclu-
ding GSD-
PDQ22
UMC100-FBP