VI150 / VI155 Parameters Continued
217
219
222
220
UMC100-FBP
Power Scale
Factor that can be used
Factor
to scale the active and
apparent power so that
the resulting value fits in a
WORD. This is needed for
bus transfer.
THD Warning
Above this level of Total Har-
Level
monic Distortions a warning
is triggered
THD Warning
Delay time until an warning is
Delay
triggered
Load Startup
Delay time until load (e.g.
Delay
pump) has started up and
power supervision functions
should become active.
0 = 1
1 = 10
2 = 100
3 = 1000
Example: U
200A, Rated PF is 0,8.
The nominal active power is then
400*200*1,73*0,8 = 110720.
To transfer this value via fieldbus
it must be scaled e.g. by 10. So
the resulting value is 110720/10
= 11072 which fits in a WORD.
3 ... 10% in steps of 1%
10 disables the function
0 ... 255 s in steps of 1s
Default is 5s
0 ... 255 s in steps of 1s
- 132 -
All excluding
GSD-PDQ22
is 400V, I
is
e
e
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22