Vi150 And Vi155 - ABB UMC100-FBP Technical Description

Universal motor controller
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

VI150 and VI155

General
Mounting
Mounting position
Dimensions (W x H x D)
LEDs: Red/yellow/green
Supply voltage
Supply current (relay activated)
Tightening torque for the input, output and supply
terminals
Tightening torque for the communication terminals See DX1xx module
Net weight
Degree of protection
Temperature range
Marks, Approvals
Operation altitude above sea level
Relay Outputs
Number of relay outputs
Voltage range of contacts
U
imp
Other technical data for the relay outputs see the DX1xx module
UMC100-FBP
Snap-on mounting onto 35 mm standard mount-
ing rails
Any.
A distance of 10 mm left and right to the
L1 and L3 terminals might be necessary depend-
ing on the other devices mounted beside for
voltages > 230 V / 400 V respectively.
22.5 x 77 x 100 mm
(excluding communication connector)
Red: Error of module
Yellow: Diagnosis available
Green: Ready for operation
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
VI150: Max. 40 mA (at 19.2 ... 31.2 V DC)
VI155: Max. 55 mA (at 19.2 ... 31.2 V DC)
See DX1xx module
0.11 kg
IP20
storage -25 ... +70 °C
operation 0 ... +60 °C
CE, cUL
Furher in preparation. Ask your local sales repre-
sentative for other marks/approvals.
VI150: max. 2000 m
VI155: max. 2000 m at 60 °C
For higher altitudes please contact your sales unit.
1
DO0 with root DOC
12-250 V AC/DC
U
=4 kV
imp
- 150 -
FieldBusPlug / Issue: 03.2012

Hide quick links: