10.3

Commissioning

10.3.1

Connection

Coaxial cable:
1.
Shield to SYN- (Ctl–) terminal
2.
Wire to
SYN+ (Ctl+) terminal
10.3.2

Alignment of the receiver module

The receiver module must be aligned to show its long side to the transmit-
ter, which is located in Frankfurt/Main in central Germany.
Minimum distances:
min. 1m to computers and monitors
min. 30cm to steel girders, metal plates and other metallic devices.
Checking the alignment
The modulation LED in the aerial enclosure of the AWS0 needs to blink
once per second. The corresponding LED on the DLX (for the control input
SYN) needs to blink in the same rhythm. Rotate the receiver module slowly
and select an alignment roughly at the center of the area with good signal
reception. If you have good reception , the DLX display will show a static
symbol " " latest after 3 minutes. A blinking symbol " " indicates disrupted
radio clock signal reception.