Meaning of individual bits:
Byte-Nr.
Bit-Nr.
Content
Byte 1
Bit 7
T-Bit
Bit 6
U-Bit
Bit 5
M-Bit
Bit 4
A-Bit
Bit 3
S-Bit
Bit 2
0
Bit 1
NP-Bit
Bit 0
L-Bit
Byte 2
0100 0000
or
aaaa mmmm
Note:
Examples for the device status in the registration period:
Device status
Bit pattern
00 40
0000 0000 0100 0000
02 40
0000 0010 0100 0000
08 40
0000 1000 0100 0000
0A 40
0000 1010 0100 0000
10 40
0001 0000 0100 0000
20 40
0010 0000 0100 0000
50 40
0101 0000 0100 0000
01 40
0000 0001 0100 0000
00 00
0000 0000 0000 0000
00 10
0000 0000 0001 0000
00 02
0000 0000 0000 0010
A 6
Explanation
Summertime switching, setting the time
Shortened registration period due to power failure or time change
Parameter change
Alarm or error message (collective message)
All warnings and device faults
Exception: Warnings 03/02 "power dip" don't stored (from version
1.04.03 up).
Transmitted during summertime (MESZ)
Unused
Power failure during the whole registration period
Unused by default
if enabled via DLXPARA: change of state of LOG control inputs
Default value $40 (hexadecimal notation);
only if enabled via DLXPARA: rate status AT-MT, however only the
energy rate (if energy values are transmitted) or the demand rate
(if demand values or energy increments are transmitted) will be
set.
S-Bit not marked(:=0) → Wintertime (:=MEZ)
Explanation
No events, wintertime
Power failure during whole period(NP-Bit=1), wintertime
No events, summertime (S-Bit=1)
Summertime (S-Bit=1), power failure during whole peri-
od (NP=1)
Alarm (A-Bit=1), wintertime
Parameter was changed (M-Bit=1), wintertime
Shortened period (U-Bit=1), Alarm (A-Bit=1), wintertime
Logic input has changed, wintertime
No events, AT1 or MT1
No events, AT2
No events, MT3